Permit Number: TS-PRM-0925-00374
Parcel: 136153850

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.2

Permit Number - TS-PRM-0925-00374
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-0925-00374 (7910 E GOLF LINKS RD TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7 and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

2. Provide the number of circuits required and the amp rating of each sign.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/23/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TS-PRM-0925-00374 (7910 E GOLF LINKS RD TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:



1. Add the following notes to each Illuminated Sigh sheet:
“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:
2. Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.
Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/25/2025 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-0925-00374 7910 E. Golf Links Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Code reference, Unified Development Code, Article 7A: Sign
Application:
1) Fill in missing information on application.

Sign Drawings:
1) Sign Designation must match application and be uniform throughout drawing in alphabetical characters, not numerical.
2) Add the number of AMPs this sign will pull when illuminated.
3) Provide a call out for what materials the wall is constructed of.
4) Specify the exact anchors that are used to hold the letters to the wall
5) Show electrical disconnect switch.
6) Add exact language to all illuminated signage:
All signs and power supply components are UL listed.
All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.
All dedicated sign circuits shall be labeled.
A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign.
As per the City of Tucson Outdoor Lighting Code the internally illuminated sign as shown on this page does not exceed the 4400k color temp.
24 hour programmable timer installed to comply with the COT outdoor lighting code.
7) As an electronic message devise the following must be added to the drawings:
No animation or scrolling allowed.
Image must stay on screen for at least one (1) minute before changing
As per the City of Tucson Outdoor Lighting Code the Electronic Message Center ss shown on this page automatically dims to 200 NITS or less from sunset to sunrise.
The EMC can not interfere with FCC communications.
We need the manufacture of the EMC to write a letter to The City of Tucson that says the following...
#1. Name of the manufacturer.
#2. The EMC model number/name
#3. [EMC Model #] is fully capable of lowering to 200 nits at night.
#4. [EMC Model #] is FCC compliant.
8) Square footage includes any colors differentiating from the background. Please include stripes in sign calculations.

Site Plan:
1) Label all roadways.
2) Sign designations must match application.