Permit Number: TS-PRM-0826-00294
Parcel: 137055270

Review Status: In Review

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0826-00294
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Outdoor Lighting Standard PENDING ASSIGNMENT
N/A Sign Post Review Express PENDING ASSIGNMENT
N/A Signs Standard PENDING ASSIGNMENT
08/11/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0826-00294 (5133 S CALLE SANTA CRUZ TUCSON, AZ 85706)



Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jorge Ruiz with any questions: jorge.ruiz@tucsonaz.gov



Add the following verbiage to each internally illuminated sing sheets.



All Signs and power supply components are UL listed. NEC 600.3.

All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.

All dedicated sign circuits shall be labeled. NEC 600.5.

A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.