Permit Number: TS-PRM-0826-00294
Parcel: 137055270

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0826-00294
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2026 Signs Standard APPROVED
08/26/2026 Sign Post Review Express PENDING ASSIGNMENT
08/12/2026 Commercial Building Standard REQUIRES RESUBMIT Please provide information on wall the sign is being mounted on.

-Type of material and finish.
08/11/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0826-00294 (5133 S CALLE SANTA CRUZ TUCSON, AZ 85706)



Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jorge Ruiz with any questions: jorge.ruiz@tucsonaz.gov



Add the following verbiage to each internally illuminated sing sheets.



All Signs and power supply components are UL listed. NEC 600.3.

All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.

All dedicated sign circuits shall be labeled. NEC 600.5.

A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.
08/12/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review: TS-PRM-0826-00294 (5133 S CALLE SANTA CRUZ TUCSON, AZ 85706)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:



Add the following notes to each Internally Illuminated Sign sheet:

“24-hour programmable timer installed to comply with the COT Outdoor Lighting Code.

The means of controlling the specific “off” curfew shall be by a 24-hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “


Provide permanent curfew “off” time sign or notice:

Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.


Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)