Permit Review Detail
Review Status: In Review
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0826-00290
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2026 | Commercial Building Standard | APPROVED | |||
| 08/18/2026 | Outdoor Lighting Standard | APPROVED | |||
| N/A | Sign Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Signs Standard | PENDING ASSIGNMENT | |||
| 08/11/2026 | Commercial Electrical Fast | REQUIRES RESUBMIT | Electrical Review: TS-PRM-0826-00290 (9630 E 22ND ST Unit:UNIT 120 TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). Contact Jorge Ruiz with any questions: jorge.ruiz@tucsonaz.gov Provide the number of circuits required and the amp rating of each sign. Provide the amp load rating of each sign, NEC 210.20. Show overcurrent protection of 20A is greater than or equal to the sign amp load, 210.20(A). |
||
| 08/06/2026 | Signs Application Completeness Express | REVIEW COMPLETED |