Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TS-PRM-0826-00290
Parcel: 136406780

Review Status: In Review

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0826-00290
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2026 Commercial Building Standard APPROVED
08/18/2026 Outdoor Lighting Standard APPROVED
N/A Sign Post Review Express PENDING ASSIGNMENT
N/A Signs Standard PENDING ASSIGNMENT
08/11/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0826-00290 (9630 E 22ND ST Unit:UNIT 120 TUCSON, AZ 85748)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jorge Ruiz with any questions: jorge.ruiz@tucsonaz.gov

Provide the number of circuits required and the amp rating of each sign.

Provide the amp load rating of each sign, NEC 210.20. Show overcurrent protection of 20A is greater than or equal to the sign amp load, 210.20(A).
08/06/2026 Signs Application Completeness Express REVIEW COMPLETED