Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0825-00342
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2025 | Commercial Building Standard | APPROVED | |||
| 08/12/2025 | Commercial Electrical Fast | APPROVED | |||
| 08/12/2025 | Outdoor Lighting Standard | APPROVED | |||
| 08/18/2025 | Signs Standard | REQUIRES RESUBMIT | Application: 1) Because this site shares parking area with another building, the allowable area is calculated based off the building elevation that houses the main entry, which is 50'. The C-3 zoning allows 3 times the frontage, so 3 x 50 =150 sq ft of allowed signage. This site is proposing 212.8 sq ft of signage, which is 62.8 sq ft more than they are permitted. Revise signage to meet the allowed 150 sq ft of signage area or submit for a master sign plan or variance request. Sign Drawings: Signs A & B: 1) Show & Specify the anchors that are used to hold the letters to the raceway. 2) Revise Standard language to include: All dedicated sign circuits shall be labeled. Sign C: 1) Fill in or provide total square footage of sign and number of AMPs the sign will pull when illuminated. 2) Revise Standard language to include: All dedicated sign circuits shall be labeled. |