Review Status: In Review

Review Details: PERMANENT SIGN REVIEW v.2

Permit Number - TS-PRM-0726-00281
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Outdoor Lighting Standard PENDING ASSIGNMENT
N/A Sign Post Review Express PENDING ASSIGNMENT
N/A Signs Standard PENDING ASSIGNMENT
08/11/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0726-00281 (5331 S CALLE SANTA CRUZ Unit:BLDG 0 UNIT 125 TUCSON, AZ 85706)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jorge Ruiz with any questions: jorge.ruiz@tucsonaz.gov

Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.

All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.

All dedicated sign circuits shall be labeled. NEC 600.5.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7, and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.


Provide the number of circuits required and the amp rating of each sign.

Provide the amp load rating of each sign, NEC 210.20. Show overcurrent protection of 20A is greater than or equal to the sign amp load, 210.20(A).
08/06/2026 Signs Application Completeness Express REVIEW COMPLETED suite number is only on first page of sign package, planner will need to address in comments if needed.