Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0726-00257
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2026 Commercial Electrical Fast APPROVED
07/27/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please review and revise the notes 1-12 and include note # 31as the referenced notes do not match the section drawing. It appears a taooge bolt is to be used however # 5. indicates - Disconnect switch to power supply. Please correct and resubmit. IBC 107.2.1


Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/14/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review: TS-PRM-0726-00257 (5447 E 22ND ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
Outdoor Lighting Review:

1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24-hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24-hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:
Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.

Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)
07/28/2026 Signs Standard REQUIRES RESUBMIT 07/28/2026 Sign Review TS-PRM-0726-00257. Plan review for the above referenced structure has been completed by Ginger Neely. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Ginger.neely@tucsonaz.gov or 520-837-5017 (voice mail only).
1. Plan set to include contractor of record, name and contact information, as listed on the permit.
2. Call out height from grade to top of sign
3. Measurements to be in feet.decimal (6.5 feet), not feet’inches” (6’-6”)
4. Standard language required on plans for all illuminated signage:
• All signs and power supply components are UL listed.
• All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.
• All dedicated sign circuits shall be labeled.
• A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign.
• 24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
• As per the City of Tucson Outdoor Lighting Code the internally illuminated sign as shown on this page does not exceed the 4400k color temp.
5. Call out for how many AMPs sign will be pulling, when illuminated
6. Elevation photo showing existing signs with a note for any signs being removed or remaining