Permit Number: TS-PRM-0726-00254
Parcel: 14044009L

Address:
7710 S WILMOT RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0726-00254
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2026 Commercial Building Standard REQUIRES RESUBMIT Requires resubmit, please note the following:

-Provide clarification on attachment of pricing marquee to existing skirting in pylon sign. How is the existing skin being attached to the new signage?
-Provide clarification on attachment of ACM to canopy.
07/14/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0726-00254 (7710 S WILMOT RD TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7, and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

2. Provide the number of circuits required and the amp rating of each sign.
3. Provide the amp load rating of each sign, NEC 210.20. Show overcurrent protection of 20A is greater than or equal to the sign amp load, 210.20(A).
07/14/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review: TS-PRM-0726-00254 (7710 S WILMOT RD TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
Outdoor Lighting Review:

1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24-hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24-hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:
Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.

Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)

2. Add the following to each outdoor digital menu-board sheet (if applicable):
“As per the City of Tucson Outdoor Lighting Code the Electronic Message Center as shown on this page shall automatically dim to 200 NITS or less from sunset to sunrise. OLC 501.5.2”.
07/27/2026 Signs Standard REQUIRES RESUBMIT FROM: Georgia Pennington, Lead Planner
DATE: 07/27/2026

COMMENTS:

1. Sign A appears to be located on a separate parcel, parcel number 140442130. Provide written property owner authorization for the proposed work on Sign A.
2. Revise the plans to provide the height of Sign A from freeway grade to the top of the sign. The plans currently show the overall height from grade; however, the height from freeway grade is required for review of the proposed freeway sign.
3. Revise the site plan to show the property lines, parcel lines, street frontage dimensions, face of curb, setbacks from the face of curb to the leading edge of each freestanding sign.
4. Clarify the full scope of work for Sign D and the fuel canopy. The plans state that new fascia and graphics will be installed on the auto fuel canopy. Clearly state whether any canopy structure, fascia, framing, panels, or supports will be modified, replaced, or added. A separate commercial alteration permit may be required for canopy/fascia work beyond sign installation.
4. Revise the plans to include the full sign area for Sign D. The color striping is part of the logo/sign design and must be included in the sign area calculation, along with the 5R logo and any other sign copy or sign background graphics.


If you have any questions, please contact me at Georgia.Pennington@tucsonaz.gov.