Review Details: PERMANENT SIGN REVIEW v.2
Permit Number - TS-PRM-0724-00322
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2024 | Signs | REQUIRES RESUBMIT | These comments were not addressed: 2) NEC: A) monument sign – standard electrical notes are missing, i.e. volts, amps, circuit – timer, UL stickers, shut off switch …. Etc. provide B) add note that use of existing power to monument planned for any replacement cabinet E) Note, if the existing nonconforming sign is kept, a change of copy may be done to the existing cabinet. That new panel would need to have light only through the text / logo, but other embellishments may be added to the sign base. Please clarify if you plan to do a change of copy or a replacement monument sign. A comment response letter is required on your next submittal. |