Permit Number: TS-PRM-0724-00322
Parcel: 114512100

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.2

Permit Number - TS-PRM-0724-00322
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2024 Signs REQUIRES RESUBMIT These comments were not addressed:

2) NEC:
A) monument sign – standard electrical notes are missing, i.e. volts, amps, circuit – timer, UL stickers, shut off switch …. Etc. provide
B) add note that use of existing power to monument planned for any replacement cabinet
E) Note, if the existing nonconforming sign is kept, a change of copy may be done to the existing cabinet. That new panel would need to have light only through the text / logo, but other embellishments may be added to the sign base.

Please clarify if you plan to do a change of copy or a replacement monument sign.

A comment response letter is required on your next submittal.