Permit Number: TS-PRM-0723-00431
Parcel: 137055290

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0723-00431
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2023 Signs REQUIRES RESUBMIT RE: TS-PRM-0723-00421 / Sportsman’s Warehouse - sign permit review

Change copy panels on all signs allowed without permit – except freeway sign – see comment below

These change copy signs can be removed from package: Signs C + D + E from the Application, Drawings & Map

1. Regarding the freeway sign panel:

Obtain written permission from the property management
Provide detailed mounting information and materials used on panel for attachment


2.Regarding both wall signs:

This entire building is only allowed 441 sq ft of wall signage.

Sign A boxed is 418 sq ft

Sign B boxed is 205 sq ft

Total wall sign area shown is 623

Your options are....

1 ) Remove the sign from the rear wall.

OR

2 ) Shrink down the wall signs so the total of both is less than 441



Regarding construction for Both Wall sign: needs more info,,,,,

1 ) Change the “attaching lags” to 3/8 in diameter and indicate the length.

2 ) Copy and paste the exact wording below onto each sheet

“24 hour PROGRAMMABLE TIMER installed to comply with the COT outdoor lighting code.”


Copy and paste the exact wording below and add to each sheet of the plan set

"As per the City of Tucson Outdoor Lighting Code the Internally illuminated sign
As shown on this page does not Exceed the 4400k color temp."

Copy and paste the exact wording below and add to each sheet of the plan set

“All signs and power supply components are UL listed.

All signs shall have UL sticker, manufacturer sticker and installer sticker,
located on the exterior of the sign for inspections.

All dedicated sign circuits shall be labeled.

A safety lock out shall be provided for all signs where the shut off switch is not
directly visible to the sign.”