Permit Number: TS-PRM-0626-00235
Parcel: 11307118C

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0626-00235
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2026 Commercial Electrical Fast APPROVED
06/23/2026 Outdoor Lighting Standard APPROVED
07/14/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0626-00235
ADDRESS/PARCEL: (10023 E OLD VAIL RD Unit:UNIT 133 TUCSON, AZ 85747)
TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. When the metal corrugated roof is cut to make way for the HSS tube being welded onto the wide flange purlin, the cantilevered end of the corrugated roof is no longer supported. Provide detail drawing resolving this issue.
2. On the upside of the roof, water damming will occur above the HSS tube. Provide detail drawing how this is to be made waterproof so that people below will not get wet by water drip.
3. Where the 3/8” thick in-line backer meet the top of the ¾: x ¾” SQ Alum. Tube support, is there enough strength so that the in-line backer will not break off free should a strong wind hits the individual letters.
4. Please resubmit.
07/15/2026 Signs Standard REQUIRES RESUBMIT FROM: Georgia Pennington, Lead Planner
DATE: 07/15/2026

COMMENTS:

1. Revise the plans to indicate whether any welding will occur in the field/on site. If field welding is proposed, provide the required special inspection information for the welding work.

If you have any questions, please contact me at Georgia.Pennington@tucsonaz.gov.