Permit Number: TS-PRM-0626-00223
Parcel: 13336014G

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0626-00223
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2026 Commercial Building Standard APPROVED
06/17/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0626-00223 (9725 E BROADWAY BL TUCSON, AZ 85748)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7, and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

2. Provide the number of circuits required and the amp rating of each sign.
06/17/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review: TS-PRM-0626-00223 (9725 E BROADWAY BL TUCSON, AZ 85748)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
Outdoor Lighting Review:

1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24-hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24-hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:
Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.

Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)

2. Add the following to each outdoor digital menu-board sheet:
“As per the City of Tucson Outdoor Lighting Code the Electronic Message Center as shown on this page shall automatically dim to 200 NITS or less from sunset to sunrise. OLC 501.5.2”.
07/10/2026 Signs Standard REQUIRES RESUBMIT 07/10/2026 Review Comments:
Sign Review TS-PRM-0626-00223 9725 E. Broadway Bl. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1. All dimensions must be FEET.DECIMAL - not FEET and/or INCHES. Ex: 5.3” = 5.25’.
2. Sign detail drawings must include the total square footage of the sign area.
3. Display C (Window Signage) does not require a permit, but keep in mind that window signs cannot occupy more than 30% of the window area per Section 7A.10.1.E of the City of Tucson Sign Code.
4. As an electronic message device the following must be added to the drawings:
No animation or scrolling allowed.
Image must stay on screen for at least one (1) minute before changing.
As per the City of Tucson Outdoor Lighting Code the Electronic Message Center ss shown on this page automatically dims to 200 NITS or less from sunset to sunrise.
The EMC can not interfere with FCC communications.
We need the manufacture of the EMC to write a letter to The City of Tucson that says the following...
1. Name of the manufacturer.
2. The EMC model number/name
3. [EMC Model #] is fully capable of lowering to 200 nits at night.
4. [EMC Model #] is FCC compliant.
5. Sight visibilty triangles are displayed incorrectly on the site plan. Please review section 10-01.5.0 of the technical standards manual of the Unifed Development Code and revise site plan to show the SVTs as required.
6. Contractor of record name and contact information is required on all pages of the sign package.