Permit Number: TS-PRM-0626-00221
Parcel: 10607028B

Address:
1351 W PRINCE RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.3

Permit Number - TS-PRM-0626-00221
Review Name: PERMANENT SIGN REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2026 Sign Post Review Express PENDING ASSIGNMENT
10/15/2026 Signs Standard REQUIRES RESUBMIT TS-PRM-0626-00221 (1351 W PRINCE RD TUCSON, AZ 85705) Plan review for the above referenced structure has been completed by Chris Niemi. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Chris Niemi Christian.niemi@tucsonaz.gov 520 837 4874

1. All dimensions of SVT triangles must be noted on site plan and match requirements of UDC section 10-01.5.0 of technical standards manual. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-12455

2. Elevation pages need to be labeled north, south, east, west, not front, rear, and side.

3. On detail drawing for MS sign please indicate location of electrical disconnect switch. Identify on sign with arrow where disconnect switch is located.