Permit Number: TS-PRM-0625-00253
Parcel: 131092290

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0625-00253
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2025 Outdoor Lighting Standard APPROVED
06/30/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-0625-00253 (1709 S CRAYCROFT RD TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Show all wiring methods in detail for all new branch circuit wiring to the new pole sign. Show basic electrical route from service panel to the sign. Conductor size/type and conduit size/type. Note wet use requirements. NEC arts; 600.5(D), 300 and 408.4.
06/25/2025 Signs Standard REQUIRES RESUBMIT Site plan:
1) Please specify which of these wall types and anchors applies to this particular wall.
2) Pole Signs are only permitted with sites that have a minimum of 225' of street frontage per Sign Code 7A.10.2.C.3.b. Revise this sign to a monument sign that meets the standards of the sign code.
3) All new freestanding signs must have sealed engineering.
4) Add detail note stating "No on-site welding to be performed"