Permit Number: TS-PRM-0625-00251
Parcel: 12213055E

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0625-00251
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2025 Signs Standard APPROVED
06/23/2025 Outdoor Lighting Standard NOT REQUIRED
06/23/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0625-00251
ADDRESS/PARCEL: (3955 E SPEEDWAY BL Unit:UNIT 108 TUCSON, AZ 85712)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. The sign detail drawing on sheet 2 of 3 does not represent the actual condition.
i. There will be a gap between the I Beam web and the aluminum backer panel.
1. This means the 2 inch screw will not be long enough to screw into the I Beam web.
ii. Please provide a detail drawing that illustrate perhaps a filler to fill the gap allowing the aluminum backer panel to be attached to the I Beam web solidly secured.
1. Please specify the correct screw length.
2. Please resubmit.
06/23/2025 Commercial Electrical Fast REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0625-00251
ADDRESS/PARCEL: (3955 E SPEEDWAY BL Unit:UNIT 108 TUCSON, AZ 85712)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. A dedicated sign circuit shall be provided and will be labeled at the circuit breaker for inspections.
2. Safety lock out to be provided where shut off switch is not visible to the sign.
3. Timing device shall be provided and set to midnight shut off.
4. The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. 403.5.2 Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted. Suggested wording is as follows: “Set off time for Sign no later than 12:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.) (NOTE: The more stringent regulation will govern).
5. Please resubmit.