Permit Number: TS-PRM-0625-00242
Parcel: 133231430

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0625-00242
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2025 Commercial Electrical Fast APPROVED
06/09/2025 Outdoor Lighting Standard APPROVED
06/11/2025 Signs Standard REQUIRES RESUBMIT Application:
1) Building Permit # TC-COM-0425-00866 needs to have fees paid and permit issued before sign permit approval can be completed. Currently it is in needs resubmittal status.
2) Change of Copy permits under 35 sq ft do not require permit. Remove Sign B from permit package.
3) Window signs are permitted as long as they do not occupy more than 30% of the window area. Remove Sign C from permit package.
4) Sign Designation must match application and be uniform throughout drawing in alphabetical characters.

Sign Drawing B:
1) All dimensions must be FEET.DECIMAL - not FEET INCHES
2) Add line indicating OAH from ground to top of sign.
3) Specify the type anchors that are used to hold the raceway to the wall.
4) Show & Specify the anchors that are used to hold the letters to the raceway.
5) Provide a call out for what materials the wall is made from. I.E. Masonry, Wood with stucco, etc...
6) Sign Designation must match application and be uniform throughout drawing in alphabetical characters. This is listed as sign A on the application.

Location Map:
1) Sign Designation must match application and be uniform throughout drawing in alphabetical characters. This should be sign A.
2) Add North Arrow