Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0625-00239
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2025 | Commercial Electrical Fast | APPROVED | |||
| 06/06/2025 | Outdoor Lighting Standard | APPROVED | |||
| 06/10/2025 | Signs Standard | REQUIRES RESUBMIT | Sign Drawings: 1) Total square footage must include the total length x total height as one continuous box. Please revise calculations to include logo. 2) Specify what materials the wall is made from. I.E. Brick, Wood, Masonry, etc... 3) Specify the type of studs that are used to hold the letters the wall. Location Map: 1) Add line and detail indicating frontage amount and box around tenant space. |