Permit Number: TS-PRM-0624-00282
Parcel: 12411021G

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0624-00282
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2024 Signs REQUIRES RESUBMIT RE: Install 2 wall signs
FOR: US Coast Guard
AT: 1800 E BROADWAY BL. Zoned C-1 (3 to 1 sign ratio)
PERMIT: TS-PRM-0624-00282
DATE: 6/28/2024
DUE DATE: 7/5/2024
REVIEWER: R. Parsons (robert.parsons@tucsonaz.gov)
CODES: Unified Development Code 7A Sign Standards (UDC), National Electrical Code 600 (NEC), Tucson – Pima County Outdoor Lighting Code (OLC), International Building Code 2018 (IBC).
1. UDC:
A. The sign area as indicated by your plans is acceptable. Thank you.
2. NEC:
A. Please provide these standard notes on each sheet: A UL sticker, installer sticker, and manufacturer sticker will be placed on each sign. All dedicated sign circuits shall be labeled.
3. OLC:
A. Please add a note that the timer will be set to shutoff at midnight per city of Tucson outdoor lighting code.
4. IBC:
A. Please indicate weep holes are present at the base of both illuminated wall signs.
General Note: Please update the contacts on the permit to include a licensed sign contractor prior to issuance.
Your sign will qualify for a self-certification inspection once permitted.
Depending on revisions submitted, further review comments may be forthcoming.
I can be reached at Robert.Parsons@tucsonaz.gov if you have any questions.