Permit Number: TS-PRM-0526-00191
Parcel: 134120080

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0526-00191
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2026 Commercial Building Standard APPROVED
05/28/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0526-00191 (8120 E BROADWAY BL TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7, and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

2. Provide the number of circuits required and the amp rating of each sign.
3. Provide the amp load rating of each sign, NEC 210.20. Show overcurrent protection of 20A is greater than or equal to the sign amp load, 210.20(A).
05/28/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review: TS-PRM-0526-00191 (8120 E BROADWAY BL TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
Outdoor Lighting Review:
1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:
Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.

Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)
06/18/2026 Signs Standard REQUIRES RESUBMIT 06/18/2026 Review Comments:
Sign Review TS-PRM-0526-00191 7125 E. Broadway Bl.. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) Address on plans does not match the address applied for in Tucson Development Center (TDC). Please review correct address with Pima County Addressing and either change the address on the drawings or submit a subrecords request throught TDC for an address change.
2) A contractor with a valid CR-38 license with the Arizona Registrar of Conrtactors and an active City of Tucson Business License is required to be added to the online permit application prior to permit issuance. Raytek Lighting LLC’s contractor license #252387 was voluntarily cancelled, according to the AZROC website.
3) Sign drawings must have the contact information on each page for the contractor of record with a valid CR-38 license with the AZROC.
4) Page 8 is a duplicate and not required. Please label roadway names on site plan page 1.
5) All dimensions must be in feet.decimal format, not feet and/or inches. Please revise all pages with incorrect format.
05/28/2026 Signs Application Completeness Express REVIEW COMPLETED