Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0526-00169
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2026 | Commercial Electrical Fast | APPROVED | |||
| 05/11/2026 | Outdoor Lighting Standard | APPROVED | Approved with comments added to plans: As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.” | ||
| 06/01/2026 | Signs Standard | REQUIRES RESUBMIT | FROM: Georgia Pennington, Lead Planner DATE: 6/1/26 COMMENTS: 1. Correct the sign area inconsistency for Sign A. The application lists Sign A as 16.3 sq. ft., but Sheet A-1 lists the total square footage as 19 sq. ft. Please revise so the dimensions, square footage, and application match. 2. Clarify the existing signs to be removed, remaining, or included for reference. The application indicates there are 3 existing signs on site and 3 existing signs to be removed, but Signs B and C appear to be change-of-copy panels in existing cabinets. Signs B and C are each listed as 29.5 sq. ft. and appear to be change-of-copy in existing cabinets. Change of copy under 35 sq. ft. does not require a permit. If you have questions, please contact me at georgia.pennington@tucsonaz.gov |