Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0526-00167
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0526-00167
ADDRESS/PARCEL: (5125 E VALENCIA CROSSING DR TUCSON, AZ 85706)TS-PRM-0526-00167 (5125 E VALENCIA CROSSING DR TUCSON, AZ 85706)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. PLEASE SUBMIT STRUCTURAL CALCULATIONS AND DETAIL DRAWINGS OF THE FOLLOWING:
a. Monument Sign: Drive thru
b. Drive-thru post and panel: online order pick-up
c. Drive-thru post and panel: drive thru waiting
d. Canopy
e. Menu Board
f. Clearance Bar
NOTE: all of the above are to be generated by an Arizona licensed structural engineer. All calculation and drawings shall be sealed/signed/dated by the Arizona licensed structural enginee.
2. Please resubmit
05/19/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0526-00167 (5125 E VALENCIA CROSSING DR TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7, and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

2. Provide the number of circuits required and the amp rating of each sign.
3. Provide the amp load rating of each sign, NEC 210.20. Show overcurrent protection of 20A is greater than or equal to the sign amp load, 210.20(A).
05/19/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review: TS-PRM-0526-00167 (5125 E VALENCIA CROSSING DR TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
Outdoor Lighting Review:
1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:
Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.

Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)
06/01/2026 Signs Standard REQUIRES RESUBMIT FROM: Georgia Pennington
DATE: 6/1/26

COMMENTS:

1. Revise the site plan to clearly label all adjacent street names. The site plan must also provide setback dimensions for all proposed freestanding, monument, and drive-through signs.

2. Revise the monument sign details and site plan to demonstrate compliance with monument sign standards. The monument sign is limited to a maximum height of 10.00 feet, measured from grade, and the plans must clearly show the height measurement from grade to the top of the sign. The monument sign is limited to a maximum sign area of 50.00 square feet per face. The site plan must also show a minimum setback of 20.00 feet, measured from the leading edge of the sign to the property line.

3. Revise the elevations to provide a separate building elevation for each proposed wall sign. Each elevation must clearly show the proposed wall sign location and include full sign dimensions, including overall width and total height.

4. Revise all sign dimensions to be shown in feet using decimal format. Do not use feet-and-inches format. For example, use 3.50 feet instead of 3'-6".