Permit Number: TS-PRM-0525-00227
Parcel: 12714003C

Address:
355 N WILMOT RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.5

Permit Number - TS-PRM-0525-00227
Review Name: PERMANENT SIGN REVIEW v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2025 Commercial Electrical Standard APPROVED
08/05/2025 Outdoor Lighting Standard APPROVED
08/12/2025 Signs Standard REQUIRES RESUBMIT Application:
1) Fill in Frontage, zoning and electrical circuit information on the application.

Sign Drawings:
1) Note states that the 4400K color temp will not be exceeded, but the Internal LED Illumination table references a Qwik Mod 2 7100K illumination, which would indicate exceeding the 4400 K color temp restriction. Please modify illumination to meet code requirements.
2) Setback for monument signs is 20' from face of curb to leading edge of sign. Please revise setbacks to meet the requirements of 7A.10.2.C.2.a.1.i.d.

Site Plan:
1) Please add setback dimensions on site plan.