Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0525-00225
ADDRESS/PARCEL: (355 N WILMOT RD TUCSON, AZ 85711)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. The Signs Standard comment is requiring sealed engineering.
a. Please add to it the structural calculation and detail drawings done by a Structural Engineer licensed in the State of Arizona.
i. Please identify the wall that the sign is being mounted to such as masonry wall and size, stud wall with stucco, concrete, etc.
ii. Provide detail drawing as to how the sign is attached to the wall.
iii. Provide information on sizing the Drilled Pier or you may use the Sign Engineering Standards for the State of Arizona (submit your selected size).
i. Provide information on sizing the Pipe and its wall thickness or you may use the Sign Engineering Standards for the State of Arizona (submit your selected size).
ii. Provide detail drawing as to how the sign is attached to the steel pipe and illustrate where they occur and how often.
iii. Please have the engineer seal/sign/date all structural documents.
2. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/28/2025 Commercial Electrical Fast REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-0525-00227 (355 N WILMOT RD TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Provide disconnect per NEC art; 600.6. Where the disconnecting means is out of the line of sight from any section that is able to be energized, the disconnecting means shall be lockable in accordance with 110.25
2. Show all wiring methods in detail for all new branch circuit wiring and feeders. Conductor size/type and conduit size/type. Note wet use requirements. NEC arts; 600.5(D), 300 and 408.4.
3. Provide/note sign grounding and bonding per NEC art; 600.7.
4. Show or notate a dedicated sign circuit per NEC art 600.5.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/28/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TS-PRM-0525-00227 (355 N WILMOT RD TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide Sign Lighting Curfew Controls Per OLC section 501.6 &403.4 and note the curfew per Table 501.5.
2. Notate on the plans that all internally illuminated signs shall have a maximum color temperature of 4400K, per OLC 501.3.2. REF Sheet 3, Specification note #2.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/04/2025 Signs Standard REQUIRES RESUBMIT Application:
1) Fill in frontage and electrical circuit information.

Sign Drawings:
1) Add frontage amount (in this case the length of the building elevation that houses the main entrance).
2) This sign is located on a different property, not owned by Banner. We will need evidence affirming that the owner of the property is granting you permission to have your sign on their property. This can be done in a few ways. An easement can be created, or a ground lease or a covenant for use of real property can be obtained. Approval will not be granted on this sign until one of these forms of permission has been submitted with the sign package.
3) New freestanding signs require sealed engineering.
4) Add the number of AMPs this sign will pull when illuminated.
5) Add the following required verbiage exactly.
a. As per the City of Tucson Outdoor Lighting Code the Internally illuminated sign as shown on this page does not exceed the 4400k color temp.
b. 24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
c. All signs and power supply components are UL listed.

All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.

All dedicated sign circuits shall be labeled.

A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign.