Permit Number: TS-PRM-0525-00227
Parcel: 12714003C

Address:
355 N WILMOT RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.3

Permit Number - TS-PRM-0525-00227
Review Name: PERMANENT SIGN REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2025 Commercial Building Standard PENDING ASSIGNMENT
07/10/2025 Commercial Electrical Standard PENDING ASSIGNMENT
07/10/2025 Outdoor Lighting Standard PENDING ASSIGNMENT
07/10/2025 Signs Standard REQUIRES RESUBMIT Application:
1) Fill In Frontage, Zoning, and electrical circuit information on application.

Sign Drawings:
1) Sign Contractor Information (Signs of the Times) needs to be added to each page of the sign package.
2) Revision letter references electrical plan notes, but there are no electrical plans attached to this submittal. Electrical detail is required showing the electrical illumination details and power disconnect switch. An email has been sent to sign contractor with example of sign drawing with information required.
3) Add Exact Copy to plans:
a. No on-site welding to be performed
b. All signs and power supply components are UL listed.

All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.

All dedicated sign circuits shall be labeled.

A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign
c. As per the City of Tucson Outdoor Lighting Code the internally illuminated sign as shown on this page does not exceed the 4400k color temp
d. 24 hour programmable timer installed to comply with the COT Outdoor Lighting Code
4) All dimensions must be FEET.DECIMAL - not FEET INCHES
07/03/2025 Signs Application Completeness Express REVIEW COMPLETED