Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0525-00220
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2025 | Commercial Electrical Fast | APPROVED | |||
| 05/27/2025 | Outdoor Lighting Standard | APPROVED | |||
| 05/28/2025 | Signs Standard | REQUIRES RESUBMIT | Application: 1) Fill in missing information as noted on application page. 2) Sign Designation must match application and be uniform throughout drawing. Where are signs E, F as noted on location map? M1 on location map should match application as "D". 3) Is Sign D a change of copy only? If so and it is under 35 sq ft, please remove from sign package as no permit will be required. If it is a replacement of channel letters, please add square footage amounts to application. 4) This site is located in PAD-15. An authorization letter from Nohe Garcia (ngarcia@bourncompanies.com) is required. Sign Drawing: Sign A: 1) Specify the anchors that are used to hold the letters to the backer panel. 2) Add a call out for what materials the wall is made from. Location Map: 1) Sign Designation must match application and be uniform throughout drawing. |