Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0525-00214
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2025 | Commercial Electrical Fast | REQUIRES RESUBMIT | Commercial Electrical Review TS-PRM-0525-00214 (9630 E 22ND ST Unit:UNIT 120 TUCSON, AZ 85748) 1. Add the following text to the sign sheets: All signs and power supply components are UL listed. All Signs shall have UL sticker, manufacturer sticker & installer sticker, located on the exterior of the sign. All dedicated sign circuits shall be labeled. A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign. |
||
| 05/22/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TS-PRM-0525-00214 (9630 E 22ND ST Unit:UNIT 120 TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Provide Sign Lighting Curfew Controls Per OLC section 501.6 &403.4 and note the curfew per Table 501.5. 2. Notate on the plans that all internally illuminated signs shall have a maximum color temperature of 4400K, per OLC 501.3.2 Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/29/2025 | Signs Standard | REQUIRES RESUBMIT | Application: 1) Application is missing from sign package. Please complete sign application and include it as page 1 of the sign package. Here is the link for the application: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Sign-Permits#section-2 2) Permits for Signs in the City of Tucson must be submitted by an Arizona licensed electrical sign contractor with the following..... A. Licensed in the state of Arizona by the Arizona Registrar of Contractors with a CR-38 license ROC license number. B. A Business License number with the City of Tucson Business License department. You can obtain a City of Tucson Business License by contacting the licensing department at license@tucsonaz.gov or 520-791-4566. Sign Drawings: 1) All dimensions must be in Feet.decimal format, not feet/inches. 2) Sign drawings should be in the proper format. An email will be sent with an example attached. There is required verbiage that must be added to the sign drawing along with elevation photos of before and after images. Any existing signage must be noted to be removed. Sign detail will be required as shown in the example drawing emailed to you. 3) Add line indicating OAH from grade to top of sign, not bottom. 4) Provide a call out for what materials the wall is made from. 5) Add exact language as called out on marked up drawings Location Map: 1) Indicate the outline of the tenant space within the building & add line and frontage length. |