Permit Number: TS-PRM-0525-00207
Parcel: 140363550

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.3

Permit Number - TS-PRM-0525-00207
Review Name: PERMANENT SIGN REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2025 Commercial Electrical Standard APPROVED
07/01/2025 Outdoor Lighting Standard APPROVED NOTE: Outdoor Lighting Special Inspection is required within the building permit TC-COM-1124-02264. This will be conducted within that building permit.
06/30/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0525-00207
ADDRESS/PARCEL: (5205 E VALENCIA RD TUCSON, AZ 85706)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. SIGN C AND E
a. Please provide a detail drawing as to what fasteners and how many for each letter are used to attach to, I assume raceway.
b. Please also illustrate on your detail drawing how raceway is attached to the wall. Do make sure to identify the type of wall the raceway is being attached to. Please specify the fastener/how often and proper structural backer installed should it be necessary.
2. SIGN H, I, F, and G
a. Please submit structural calculation and detail drawings that are sealed/signed/dated by an Arizona licensed structural engineer. Or use the Sign Design Engineering Standards for the State of Arizona and select the appropriate caissance sizes and steel tube sizes.
3. SIGN J
a. Please submit structural calculation and detail drawings that are sealed/signed/dated by an Arizona licensed structural engineer.
b. Steel pipe is called out as zero diameter. Please provide the correct size.
c. There are no information as to the anchor installed in concrete. Please provide the size, length and embedment into the concrete.
d. Top of pole is shown blank. Please provide a detail drawing as to what is used to attached the top of the sign to the steel pipe. I welding used, is a saddle used, etc?
e. I sign cabinet bottom itself attached to the concrete base, if so provide detail drawing.
4. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
06/17/2025 Signs Standard REQUIRES RESUBMIT Application:
1) This Sign Package is missing the Application.
The Application should be PAGE ONE of every Sign Package. Sign designation on application should match throughout drawings.

Sign Drawings:
A, B, D, E
1) Add exact wording:
As per the City of Tucson Outdoor Lighting Code the internally illuminated sign as shown on this page does not exceed the 4400k color temp.

D/E Page Only:
1) Remove the E designation as this is shown on a separate page.

H/I, F/G
1) Add exact wording:
The EMC will not interfere with FCC communications.
2) Supply a letter from the manufacturer of the EMC to The City of Tucson that says the following...

#1. Name of the manufacturer.
#2. The EMC model number/name
#3. [EMC Model #] is fully capable of lowering to 200 nits at night.
#4. [EMC Model #] is FCC compliant.

J
1) Add exact verbiage:
All signs and power supply components are UL listed.

All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.

All dedicated sign circuits shall be labeled.

A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign

Site Plan:
1) Add distance from front of curb to leading edge of freestanding sign J.