| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2025 | Commercial Electrical Fast | REQUIRES RESUBMIT | Commercial Electrical Review TS-PRM-0525-00184 (7111 E 22ND ST TUCSON, AZ 85710) 1. The pages are blurry and some of the electrical specification notes are not legible. 2. Show all wiring methods in detail for all new branch circuit wiring and feeders. Conductor size/type and conduit size/type. Note wet use requirements. NEC arts; 600.5(C), 300 and 408.4. 3. Sheet 3 of 7, Drive-thru Canopy detail shows a Electrical Feed by Installer. Clarify if new electrical is being installed, or if existing electrical cirucits are being used. 4. The currently adopted codes are not noted on the plans. The City of Tucson has currently adopted the 2017 NEC and 2018 IBC. |
||
| 05/12/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TS-PRM-0525-00184 (7111 E 22ND ST TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. As per the City of Tucson Outdoor Lighting Code the Electronic Message Center as shown on this page automatically dims to 200 NITS or less from sunset to sunrise. OLC 501.5 2. Provide Sign Lighting Curfew controls Per OLC section 501.6 &403.4 and note the curfew per Table 501.5. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/05/2025 | Signs Standard | REQUIRES RESUBMIT | Application 1) Fill in missing information on application as indicated. Sign A drawing: 1) Add verbiage stating "No onsite welding." 2) Is this an electronic message display? If so, the following must be added to the drawings: No animation or scrolling allowed. Image must stay on screen for at least one (1) minute before changing. As per the City of Tucson, Outdoor Lighting Code the, Electronic Message Center As shown on this page automatically, Dims to 200 NITS or less from sunset to sunrise. The EMC can not interfere with FCC communications. We need the manufacture of the EMC to sit down and write a letter to The City of Tucson, That says the following... #1. name of the manufacturer. #2. the EMC model number/name #3. - This model is fully capable of lowering to 200 nits at night. #4. This model is FCC compliant. 3) All dimensions must be in feet.decimal, not feet inches. 4) Indicate whether you are using the existing menu board foundation or digging new. 5) Add sign company information to drawings (Monster Signs). |