Permit Number: TS-PRM-0525-00177
Parcel: 11515197A

Address:
1901 N ORACLE RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0525-00177
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2025 Commercial Building Standard APPROVED
05/09/2025 Outdoor Lighting Standard APPROVED
05/09/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-0525-00177 (1901 N ORACLE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Sign B shows 2-20 amp circuits 120V and 1-20 amp circuit 220V. For new circuits, provide the following information below:
2. Provide details on how new electrical circuits are being routed to the sign, [NEC 230.30]. Provide burial depth, conduit size, wet condition.
3. Show all wiring methods in detail for all new branch circuit wiring and feeders. Conductor size/type and conduit size/type. Note wet use requirements. NEC arts; 600.5(D), 300 and 408.4.
4. Provide/note sign grounding and bonding per NEC art; 600.7.
5. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4.
6. Show dedicated sign circuit per NEC art 600.5.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/05/2025 Signs Standard REQUIRES RESUBMIT Sign Drawings

1 )Indicate whether the caisson is new or existing.
2)10' OAH on freestanding sign needs to have a note that the OAH measurement is being measured from the top of curb to the top of the sign.
5) May require site specific letter from manufacturer re: FCC compliancy and sign meeting standards.
5) Need total amperage the whole freestanding sign is.

Location Map
1) Need to show SVT dimensions of 20' x 345'
2) Your submittal requires additional information for the freestanding sign
A scaled COT approved site plan indicating:
Property lines,
Sight visibility triangles,
Proposed and existing right of way,
Location of sign on property,