Permit Number: TS-PRM-0426-00143
Parcel: 131090090

Address:
5740 E 22ND ST

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0426-00143
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2026 Signs Standard APPROVED
05/07/2026 Commercial Electrical Fast NOT REQUIRED Change of Copy only. No change in the outdoor lighting or electrical.
05/07/2026 Outdoor Lighting Standard NOT REQUIRED Change of Copy only. No change in the outdoor lighting or electrical.
05/18/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0426-00143
ADDRESS/PARCEL: (5740 E 22ND ST TUCSON, AZ 85711)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. WALL SIGN
a. Mounting detail drawing is not present within the drawings.
b. Please provide/submit a detail drawing illustrating the type of fastener used appropriate to the type of wall at the job site (show type of wall and its components), how many or how often, embedment depth, et.
2. MONUMENT SIGN
a. Please provide basic information such as the size of the pipe used as post, the size of the footing, etc.
b. Please provide/submit a detail drawing illustrating the type of fastener used to attach and appropriate to the monument sign construction, how many or how often, embedment depth, et.
3. Please resubmit.