Review Date Reviewer's Name Type of Review Description Status Comments
N/A Commercial Building Standard PENDING ASSIGNMENT
04/30/2026 Commercial Electrical Fast REQUIRES RESUBMIT Electrical Review: TS-PRM-0426-00140 (9015 E TANQUE VERDE RD TUCSON, AZ 85749)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7 and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.
04/30/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review: TS-PRM-0426-00140 (9015 E TANQUE VERDE RD TUCSON, AZ 85749)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
Outdoor Lighting Review:
1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”

“24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “

Provide permanent curfew “off” time sign or notice:
Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.
Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)
05/12/2026 Signs Standard REQUIRES RESUBMIT 05/12/2026 Review Comments:
Sign Review TS-PRM-0426-00140 9015 E. Tanque Verde Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) Please show the frontage lengths on the site plan so determination of total allowable square footage can be determined.
2) All freestanding signs must show the distance from the face of the adjacent right of way curb to the leading edge of the sign on the site plan.
3) All new freestanding signs must have sealed engineering.
4) All illuminated signs, including freestanding signs, are required to show the location of the electrical disconnect switch.
5) All dimensions must be in feet.decimal format, not feet and/or inches.
6) All electrical signage needs to have the following exact language on the sign drawings:
All signs and power supply components are UL listed.
All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.
All dedicated sign circuits shall be labeled.
A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign.
24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
As per the City of Tucson Outdoor Lighting Code the internally illuminated sign as shown on this page does not exceed the 4400k color temp.
7) The total number of AMPs the illuminated sign will pull when illuminated needs to be noted on the drawings.
8) For signs D and E, please list the specific materials the wall/canopy the sign is being attached to is constructed of. Include all materials including the structure of the wall, not just the finishing materials like stucco.
9) Please specific the type, size and number of the anchor being used to attach the signs to the wall. Attachment must meet the requirement of the 2018 IBC 3107.1 Signs and Chapter 1603.1.4. The primary requirements for such signs will be related to structural stability as addressed in Chapter 16 and IBC Appendix H.
10) The dimension for the calculated sign area for signs F & G needs to be shown on the drawings. The noted sign area of 1.64 sq ft does not match the dimensions called out on the drawings.