Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.2
Permit Number - TS-PRM-0426-00117
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2026 | Signs Standard | REQUIRES RESUBMIT | 05/15/2026 Review Comments: Sign Review TS-PRM-0426-00117 5997 E. Grant Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049. 1. Please provide all of the materials the wall is constructed of, not just the finishing material, stucco. 2. Indicate the outline of the tenant space within the building on the site plan. 3. Double sided tape is not sufficient to hold the sign to the wall against wind loads. Please provide the necessary fasteners, detail drawings or hire a structural engineer to specify the fastener type, the structural calculation and detail drawings that meets the requirements of the 2018 IBC 3107.1 Signs and Chapter 1603.1.4. The primary requirements for such signs will be related to structural stability as addressed in Chapter 16 and IBC Appendix H. |