Permit Number: TS-PRM-0425-00132
Parcel: 11709111B

Address:
430 W 22ND ST

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.3

Permit Number - TS-PRM-0425-00132
Review Name: PERMANENT SIGN REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2025 Commercial Electrical Standard APPROVED
06/03/2025 Outdoor Lighting Standard APPROVED
06/16/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TS-PRM-0425-00132

ADDRESS/PARCEL: (430 W 22ND ST TUCSON, AZ 85713)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. Please provide structural calculation and detail drawings sealed/signed dated by an Arizona licensed structural engineer or you may use the Sign Design Engineering Standards for the State of Arizona.
a. This to provide proof that the drilled pier and the pipe used are sized correctly.
b. Provide drawing illustrating how the aluminum base is attached to the steel pipe and how often does it occur.
c. Provide detail drawing illustrating how the sign cabinet is attached to the aluminum base.
d. Provide drawings how the sign cabinet is attached to the steel pipe and how often.
2. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/30/2025 Signs Standard REQUIRES RESUBMIT Sign Drawings:
1) Need call out on how many AMPs the sign will be pulling.

Site Plan:
1) This is a plot plan, not an approved City of Tucson Site Plan. You will need to obtain one by submitting a request through TDC, similar to applying for a permit. The site plan needs to show approval stamps from the City of Tucson and should be scaled, with a north arrow and the site address. The sign must be show on the site map in proper scale. An email with an example of a proper site plan will be sent.