Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2023 Signs REQUIRES RESUBMIT A permit application is missing from the package

Add all outdoor lighting code notes, timer, midnight curfew, 4400k max brightness, all manufacturer, installer and UL stickers on all signs
label shut off, call out all volts, amps, circuits
state that a dedicated sign circuit will be provided and shall be labeled at the breaker panel
all dimensions shall be in decimal feet
all mounting information shall be clearly called out with appropriate size / type of mount to the type of wall (ID that as well - i.e. frame /stucco or block - give both types of mounts if you are unclear on wall type)
review will be done when sufficient information is provided