Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0326-00088
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2026 | Commercial Electrical Fast | APPROVED | |||
| 03/10/2026 | Outdoor Lighting Standard | APPROVED | |||
| 04/03/2026 | Signs Standard | REQUIRES RESUBMIT | Sign Review TS-PRM-0326-00088 103 N. Pantano Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049. 1) All dimensions must beet in feet.decimal format, not feet or inches. Ex. 1’9”= 1.75’ or 163.5” = 13.63’. 2) Contractor on record (Flash Electric & Sign) must have name and contact information listed on drawings. 3) Please provide the type of material the wall is constructed of so that the efficiency of the attachment method can be determined. Please include all materials, not just finishing materials like stucco. 4) Provide the outline of the tenant space within the building on site plan and indicate tenant frontage, not the entire building frontage. 5) Provide a call out for the electrial disconnect switch. |