Permit Number: TS-PRM-0325-00095
Parcel: 10120038C

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0325-00095
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide structural design, calculations and construction drawings, prepared by an Arizona licensed design professional for the 35 ft tall Freeway sign; and the Wall Sign. IBC 107.2.7
2. Please list any required Special Inspections on the plans.
Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. for any required special inspections. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/16/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-0325-00095 (3150 W EL CAMINO DEL CERRO TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work.
Plans shall include, but may not be limited to items below:
3. Provide a line diagram showing the connection from the main service entrance to the appropriate service entrance and sub-panels, NEC 110.2, 2018 IBC 107.1. Note any new or modified electrical or branch-circuits.
4. Provide new and updated panel schedules, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4.
5. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.

6. Provide electrical load calculations, for the Main Service Panel and Sub-panels, Per NEC 220.40.

7. Show compliance with the outdoor lighting code, chapter 5. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Additional comments may be forthcoming based on a complete plan-set.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
04/03/2025 Signs Standard REQUIRES RESUBMIT FROM: Georgia Pennington, Lead Planner
DATE:4/3/2025

COMMENTS:

(I have emailed applicant a template to use on next submittal)

1. Provide property lines on site plan. It appears as if the proposed location of the freeway sign is near a property line.

2. Provide height from freeway grade to top of sign.

3. All dimensions must be in feet-decimal form.

4. Provide a scale on each page.

5. Include electrical details and Outdoor Lighting Code information.

6. Label the signs as "A" and "B" to match the application sheet.

7.Regarding wall sign, provide information regarding wall materials and specific anchor information.

8. Remove red lettering disclaimer on all pages.

9. Correct application form to say "freeway" instead of "pole".