Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TS-PRM-0324-00106
Parcel: 12217003B

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0324-00106
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2024 Signs REQUIRES RESUBMIT RE: Manufacture & Install 1 set of LED Illuminated pan channel letters mounted on building fascia
FOR: Brucha
AT: 3435 E Speedway Blvd Zone: C2 (3 to 1 sign ratio)
PERMIT: TS-PRM-0324-00106
DATE: 4/11/2024
REVIEWER: R. Parsons (robert.parsons@tucsonaz.gov)
CODES: Unified Development Code 7A Sign Standards (UDC), National Electrical Code 600 (NEC), Tucson – Pima County Outdoor Lighting Code (OLC), International Building Code 2018 (IBC).
1. UDC:
A. The sign area as proposed is acceptable. Thank you.
B. Please include sign C on your sign permit application. It appears you only have A and B listed.
2. NEC:
A. Please add power details for each sign (i.e: amps, volts, circuits).
3. OLC:
A. Please add a note that the timer will be set to shutoff at midnight.
B. Please add a note that maximum color temperature will not exceed 4400K per Outdoor Lighting Code.
4. IBC:
A. Please specify wall construction material.
B. Please specify the size and number of fasteners per sign.
Your sign will qualify for a self-certification inspection once permitted.
Depending on revisions submitted, further review comments may be forthcoming.
I can be reached at Robert.Parsons@tucsonaz.gov if you have any questions.