Permit Number: TS-PRM-0226-00079
Parcel: 140122150

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0226-00079
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2026 Commercial Electrical Fast APPROVED
03/02/2026 Outdoor Lighting Standard APPROVED
03/19/2026 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-0226-000079 5005 S. Campbell Av. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) The following exact copy language needs to be included on the drawings:
⦁ All signs and power supply components are UL listed
⦁ All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections
⦁ All dedicated sign circuits shall be labeled
⦁ A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign
2) Specify which construction guidelines are being utilized for the attachment of the sign as listed on page 4 of the drawings.