Permit Number: TS-PRM-0226-00058
Parcel: 13316048B

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0226-00058
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2026 Commercial Electrical Fast APPROVED
02/19/2026 Outdoor Lighting Standard APPROVED
03/11/2026 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-0226-000058 6410 E. Tanque Verde Rd. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) New freestanding signs or reuse of an existing foundation for a new sign requires sealed engineering.
2) New freestanding signs require the last approved site plan. Site plan needs to show the setback from the leading edge of the sign to the front of curb. Site plan also needs to show sight visibility triangle for both the near and far side. Please review Section 10-01.5.0 of the UDC and adhere to the requirements found there.
3) Provide the number of AMPs the sign will pull when illuminated.