Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0223-00206
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2023 Signs REQUIRES RESUBMIT RE; wall sign review
For: Eric's Watch Repair
AT: 9095 E Tanque Verde Rd / Scenic Sign District
Permit: TS-PRM-0223-00206
Reviewer: H. Thrall (Heather.Thrall@tucsonaz.gov)
Date: 03/08/22

Codes; Unified Development Code (UDC) 7A Sign Standards, National Electrical Code (NEC) 600, Tucson-Pima County Outdoor Lighting Code (OLC) and International Building Code (IBC) 2018

1. UDC:
A) sign area is allowed, thank you - please note, with the landlord permission - you may actually INCREASE the client's sign area to 25 square feet per UDC 7A.11.3 scenic district, for establishments with less than 20' of frontage...

2) NEC / OLC:
A) list volts
B) List amps the sign is pulling
C) list number of circuits
D) add note that a dedicated sign circuit shall be provided and will be labeled at the breaker panel
E) add note that the sign shut off switch will have a lock out
F) add note that the sign shut off shall be at midnight via the timer provided

3) IBC:
A) no comments, thank you

Please update the electrical and outdoor lighting code comments on your construction sheet. Please then upload ALL the documents onto the portal, the permit application, the construction / elevation sheet, and the location plan. Please email me when you upload, and I'll pull the resubmittal faster.