Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2026 Commercial Electrical Fast APPROVED
01/28/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1125-02157
ADDRESS: (910 W IRVINGTON RD TUCSON, AZ 85714)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. SIGN A & C on the building.
a. The mounting detail drawing is missing for both signs listed above.
a. Please indicate the wall material sign is attached to.
b. Indicate the type of fastener used and how often or how many per letter.
2. SPECIAL INSPECTION FORM
a. The special inspection for the building sign that are 30 ft above grade are listed.
b. However, the Pylon sign that are 30 ft are not listed.
a. Please add the welding special inspection for the pylon sign.
3. PYLON STRUCTURE
a. The structural calculation and detail drawings are missing. The following are your options.
a. Respond to these comments and submit the structural calculation for the pylon structure with this sign permit. This to include foundation/footing, anchoring used, detail drawing, connection details illustrating fasteners used, structural member size calculations, electrical power, etc. Ensure that these documents are sealed/signed/dated by the Arizona licensed structural engineer.
b. Apply for a separate permit for this pylon structure. Submit the building permit number in order for the city to verify its existence.
c. Should it be already permitted, please provide the building permit number allowing the city to view the approved drawings.
4. Please resubmit.
01/07/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TS-PRM-0126-00001 (1500 E TUCSON MARKETPLACE BL TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. There are several signs that have a color temperature listed at 7000K under the ‘Finish Specifications’ notes. These internally illuminated signs shall not exceed the color temperature of 4400K, OLC 501.3.2.” Please provide updated plans and ‘Finish Specifications’ notes that clearly show compliance with the Outdoor Lighting Code color temperature requirements for internally illuminated signs, OLC 501.3.2.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/22/2026 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-0126-00001 1500 E. Marketplace Bl. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) Several sign details call out 7000K LED, which exceeds the allowed 4400K limit required by code. Please reconfigure to meet Outdoor Lighting Code 501.3.2.