Permit Number: TS-PRM-0125-00038
Parcel: 141185990

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.4

Permit Number - TS-PRM-0125-00038
Review Name: PERMANENT SIGN REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2025 Commercial Building Standard APPROVED
04/24/2025 Signs Standard REQUIRES RESUBMIT Wall Sign Comments:
1) Attaching hardware must be specifically noted as to type and size and must match engineering.
2) Verify actual amperage on all signs with manufacturer as all signs are noted as pulling the same amperage and signs vary greatly in size.
3) All signs need to designate the type of material (wall-i.e. masonry or wood frame with stucco etc... or canopy- i.e. metal canopy frame) that they are attaching to.