Permit Review Detail
Review Status: Requires Resubmit
Review Details: RIGHT-OF-WAY REVIEW v.3
Permit Number - TR-ROW-1225-01461
Review Name: RIGHT-OF-WAY REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2026 | Transportation Application Review Express | PENDING ASSIGNMENT | |||
| 03/06/2026 | ROW Engineering Review - Standard | REQUIRES RESUBMIT | I believe that I see conflict & Discrepancy between the site plan provided and the traffic control plan. Traffic Control plan and Red/Blue lines called out on design plan as located on the Pima St side of the project. Site/Design plans calls out the Water Connection - "Connect to Exisiting Water, Sawcut, Pavement to be removed and replaced in Kind". This location of work is on the Alvernon way side of the project just south of the Entry Driveway. Please review all documents and then re-upload corrected plans showing and calling out accurate location. I will be placing the current request in Resubmittal status and marking all files requiring re-upload.. |