Permit Review Detail
Review Status: Requires Resubmit
Review Details: RIGHT-OF-WAY REVIEW v.2
Permit Number - TR-ROW-0625-00781
Review Name: RIGHT-OF-WAY REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2025 | ROW Engineering Review - Standard | REQUIRES RESUBMIT | Review Traffic Control design based on proposed Scope of Work for "Curb Cut, per PAG". Double lane closure should not be required per scope of work. Review Notes: 1) TCP - Double Lane closure? Provide explanation of Needs 2) TCP - Show/Call out Pedestrian accommodation/Access during proposed work (Note Pedestrian may not travel more that 660' to marked ADA compliant crossing from work zone, before on site pedestrian accommodations are required) 3) TCP - Show/Call out Bicycle lane access/Accommodate during proposed work (Note Bike may not share travel lane at POSTED speed limits above 30 mph) 4) Call out work hour and closure hours on Traffic Plan 5) Site plan - Call out and show Proposed work area on Aerial Site plan. |
||
| 06/10/2025 | Transportation Application Review Express | REVIEW COMPLETED |