Review Date Reviewer's Name Type of Review Description Status Comments
Entitlements * REVIEW COMPLETED After researching the proposed use, it would fall under the Utilities Distribution Land Use, which is allowed in the RX-1 as a Zoning Examiner Special Exception.

The Special Exception would be supported by Plan Tucson polices guiding the thoughtful placement of utilities infrastructure in a manner ensuring compatibility with existing neighborhoods. The existing site is developed with Utilities Distribution and Wastewater Treatment facilities, and augmenting the existing Distribution with the Advanced Water Purification Facility adds to and enhances the existing Utilities Distribution facilities at the site.

The Zoning Examiner Special Exception requires that a neighborhood meeting be held with labels generated by PDSD, and a hearing before the Zoning Examiner not more than 70 days after the application is accepted. The Zoning Examiner renders a final decision no more than 10 business days following the hearing.
Fire New Construction * REVIEW COMPLETED TP-PRE-0926-00196 • Pre-Application Conference Review v1 • 2550 W SWEETWATER DR TUCSON, AZ 85705:
Please see below in reference to the requested information.
5. Will Fire and Life Safety be reviewed and...
Fire and Life Safety reviews are routed to TFD where applicable for each submittal.
6. What are current plan review...
Fire reviews are currently 2-4 weeks out.
7. Are deferred submittals such as Fire...
TFD prefers these systems to be submitted by the installing subcontractor.
Reach out with any additional fire related questions.
Questions: patricia.shelton@tucsonaz.gov
Historic * REVIEW COMPLETED The project is considered a federal undertaking. Design plans are subject to cultural resource consultation, which will be initiated by the Bureau of Reclamation. The project area is located within an archaeological sensitivity zone. The project should anticipate that cultural resource compliance activities must be completed before any construction begins.
ROW Engineering Review * REVIEW COMPLETED DTM Review Comments -
Based on the proposed scope of work and work location DTM has no direct comments at this time. More in depth review to be performed when Development and Design plan package is submitted.
DTM will be present at the Pre-Activity meeting for question that come up.
Site Engineering * REVIEW COMPLETED Permit Activity Number: TP-PRE-0926-00196
Project: Discussion on the proposed Tucson Advanced Water Purification Facility. Topics of discussion to include: Plan Submittal format, Zoning, site layout, and more
Location: 2550 W SWEETWATER DR
Review Date: 10/15/2026
Reviewer: Marco Contreras & Joe Macaulay
Related Cases: XXX

*This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-6 and Technical Standards Manual (TSM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code.*
City of Tucson Code: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes
Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage-manual-searchable.pdf
Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-retention-detention-manual.pdf
Site Engineering Review Comments:
1. Application Question #1 - If area of disturbance is greater than one acre, it will be required that a SWPPP be prepared and submitted at time of submission of the development package submission. The official dust control permit through Pima County would need to be issued prior to the issuance of the development package permit.
2. Application Question #5 - At time of review for the development package submission, Tucson Fire will be an assigned reviewer.
3. Application Question #6 – DP Intake 1-4 days, official full queue review cycle is 21-days, and each subsequent review cycle would follow the 21-day timetable.
4. Application Question #8 – Each individual structure will require its only commercial building permit for review and approval.
5. The proposed development must comply with the City of Tucson Unified Development Code (UDC) Administrative Manual Chapter 2-06 – Development Package. Building permits can be submitted and reviewed concurrently with the development package but the building plans cannot be approved until the development package is approved and the building plans are reviewed for consistency.
6. A drainage report shall be submitted with the application for the associated development package submittal. The report must demonstrate compliance with all applicable City of Tucson stormwater management requirements, including first-flush retention and critical basin detention. The following references from the Standards Manual for Drainage Design and Floodplain Management (COT Drainage Manual) and the Design Standards for Stormwater Detention and Retention Manual (DSSDR) shall govern report preparation:
a. Report Formatting & Content: COT Drainage Manual §2.3; DSSDR Chapter 10
b. Flood Peak Estimation: COT Drainage Manual Chapter 4
c. Erosion Hazard Assessment: COT Drainage Manual Chapters 6 & 7
d. Drainage Facility Design Standards: COT Drainage Manual Chapters 9–11
e. First-Flush Retention & Detention Guidelines/Triggers: DSSDR Chapters 2, 3, & 4
7. Geotechnical Investigation Report — A Geotechnical Investigation Report prepared and sealed by a Professional Engineer registered in the State of Arizona is required [IBC 1803] and shall be submitted with the associated Development Package submittal. At a minimum, the report shall address the following:
a. Soil Bearing Capacity & Site Classification — Allowable soil bearing capacity, seismic site classification, expansive soil identification, and groundwater conditions, with all applicable foundation design recommendations for the proposed construction.
b. Grading & Earthwork — Recommendations for site preparation, fill compaction standards, and the suitability of on-site materials for reuse as engineered fill.
c. Pavement Design — Pavement design recommendations for all proposed drive aisles, parking areas, and access improvements, including R-value or CBR test results as applicable.
d. Retaining Walls (if applicable) - Backfill requirements and wall foundation recommendations.
e. Drainage Manual 14.2.6 Items — Soil classification, soil erodibility, soil permeability and infiltration rate, slope stability, and groundwater elevation; a recommended minimum setback from buildings and other structures; an evaluation of whether hydro-collapsing soils are present on the site; and the boring log(s) and laboratory results supporting the above based on the required 30-foot boring test.
8. Grading and Stormwater — The Development Package submittal shall include a grading plan showing both cut and fill quantities (cubic yards) and the total area of disturbance, expressed in both square feet and acres. [TSM 2-01.0.0]
a. Where the total area of disturbance is one (1) acre or more — or is part of a larger common plan of development that will ultimately disturb one acre or more — coverage under the AZPDES Construction General Permit is required. The applicant shall prepare a Stormwater Pollution Prevention Plan (SWPPP) and file a Notice of Intent with ADEQ prior to the start of any earth-disturbing activity.
b. A dust control permit from the Pima County Department of Environmental Quality is required separately and is triggered at the same threshold as the SWPPP. Confirm applicability with PDEQ prior to commencing site work.
9. Applicable Waste Management Standards:
a. Provide the Waste Stream Calculations for the entire site on the Development Package cover sheet or where able to on the plan set. [TSM 8-01.8.0]
b. All commercial developments are required to provide adequate space/capacity for both solid waste & recycling services [TSM 8-01.5.1.A]
c. Provide a trash enclosure detail(s) that is compliant with TSM 8-01.0.0. This should include all necessary information as well as include the required minimum clear space. This detail should be comparable to figures found in TSM 8-01.9.0.
d. Provide a detail displaying trash truck maneuverability for the trash enclosure in compliance with Technical Standards Manual, show it falls in compliance with back-up requirements. Maneuverability dimensions for operation are 14’x40’ & 28’x40’ for two enclosures. TSM 8-01.5.3 and TSM 8-01.5.3.F
10. Sidewalks shall be flood free for all storm discharges of up to and including a ten-year frequency flood event. Drainage flowing across all pedestrian circulation paths shall be designed and constructed to convey flows under the path for up to and including the ten-year frequency flood events, except at street intersections, pedestrian crossings, and PAAL pedestrian crossings. [TSM 7-01.4.1.E & 7-01.4.3.E]
a. Provide keynotes and call-outs identifying all downspouts and sidewalk scupper locations on all related site plans and/or building sheets. This information is required to demonstrate compliance and to ensure coordination with building permit plan review.
b. If downspouts from rooftops are to be discharged at grade-level, ensure that the stormwaters up to and including flow from a 10-year event are directed away from accessible parking stalls.

*NOTICE: These comments are provided for pre-application purposes only and are based solely on the conceptual information submitted to date. This review does not constitute an approval, and compliance with these comments does not guarantee approval of a subsequent submittal. Additional comments, including comments on items not addressed here, may be issued during formal review of the Development Package as more detailed plans become available.*



If you have any questions or concerns, please contact marco.contreras@tucsonaz.gov
Site Landscape * REVIEW COMPLETED PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, PLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: PROPOSED TUCSON ADVANCED WATER PURIFICATION FACILITY; PLAN SUBMITTAL FORMAT; ZONING; SITE LAYOUT
ACTIVITY NO: TP-PRE-0926-00196
ADDRESS: 2550 W SWEETWATER DR
ZONING: RESIDENCE ZONE (RX-1)
LAND USE PER UDC TABLE 7.6.4-1: UTILITY SERVICE
10.13.2026

THE COMMENTS PROVIDED ARE PRELIMINARY AND ARE NOT TO BE ASSUMED AS A COMPLETE REVIEW OF THE PROPOSAL. DURING THE DEVELOPMENT PACKAGE REVIEW PROCESS, A FULL REVIEW WILL BE MADE BY THE SITE LANDSCAPE/NPPO REVIEW SECTION TO ENSURE COMPLIANCE WITH THE APPLICABLE CITY OF TUCSON UNIFIED DEVELOPMENT CODE, TECHNICAL STANDARDS MANUAL AND ADMINISTRATIVE MANUAL REQUIREMENTS FOR SITE LANDSCAPE, NATIVE PLANTS AND RAINWATER HARVESTING.

SITE LANDSCAPE/NPPO COMMENTS:

1. This is an existing site, and the scope of work or expansion is not clear. Once the area of expansion or level of improvements are indicated, a full review will be provided by the site landscape review section. If there is an expansion in square footage of land area, floor area, lot coverage, or vehicular use area of greater than 25 percent, then UDC 7.6 landscape and screening standards may apply. If UDC 7.6 standards are required, this will trigger the commercial rainwater harvesting ordinance.

2. FOR REFERENCE TO EXPANSIONS AND SITE LANDSCAPE REQUIREMENTS:
UDC 7.6.2. APPLICABILITY
The provisions of this section apply to the following:
A. All new development; and,
B. Expansion of existing development, as provided below:
1. Buildings Greater Than 10,000 Square Feet
On sites where the gross floor area of the existing building (s) is more than 10,000 square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows:
a. If the expansion is less than 25%, the standards of this section apply only to the proposed expansion. Existing development on the site is subject to the zoning standards in effect at the time the existing development received zoning approval.
b. If the expansion is 25% or greater or if expansion as of February 15, 1991, cumulatively result in a 25% or greater expansion in land area, floor area, lot coverage, or vehicular use area, the standards of this section apply to the entire site. Preparation of the landscape plan shall adhere to UDC 7.6.4 and Administrative Manual 2-10.

3. No other comments or concerns with this project site at this time.

Thank you.

CHAD KELLER, PLA
LANDSCAPE ARCHITECT

CITY OF TUCSON, PDSD, SITE REVIEW SECTION
CHAD.KELLER@TUCSONAZ.GOV
520.837.4923
Site Zoning * REVIEW COMPLETED CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Jeffrey Cassidy; Planner

PROJECT: TP-PRE-0926-00196
Address: 2550 W Sweetwater Dr, Tucson, AZ 85705
Parcel(s): 103-06-092J
Zoning: RX-1
Existing Use: Utilities Use Group – Sanitation System
Proposed Use: Utilities Use Group – Distribution System as a Water Pumping and Storage Facility

TRANSMITTAL DATE: Thursday, October 15, 2026

COMMENTS:
1. The Development must comply with Administrative Manual – 2-06, Development Package. Building permits can be submitted and reviewed concurrently with the development package but the building plans cannot be approved until the development package is approved and the building plans are reviewed for consistency.

2. The site is zoned RX-1. The proposed use is Distribution System, which, per Zoning Examiner Special Exception Procedure, Section 3.4.3 https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-1048 , is subject to use specific standards 4.9.11.A. 1, .2, .5, .8, .9, .11, .12. Refer to Comment #3.

Use Specific Standards:

4.9.11.A.1: The setback of the facility, including walls or equipment, shall be 20 feet from any adjacent residential zone.

4.9.11.A.2: Where a facility is not enclosed within a building, the surrounding screen shall be used as the building wall for the purposes of setbacks.

4.9.11.A.5: The use shall not have any service or storage yards.

4.9.11.A.8: Any building housing such facility shall be in keeping with the character of the zone in which it is located. The Design Review Board (DRB) shall review all applications and make recommendations to the Zoning Examiner. The DRB shall review architectural style, building elevations, materials on exterior facades, color schemes, new mechanical equipment locations, lighting of outdoor areas, window locations and types, screening, landscaping , vehicular use areas , and other contributing design features.

4.9.11.A.9: The use shall be located wholly within an enclosed building or within an area enclosed on all sides with a masonry wall or compact evergreen hedge, not less than six feet, nor more than ten feet, in height.

4.9.11.A.11: The use shall be limited to water pumping and storage facilities, telephone exchanges, and power substations with an input voltage of no greater than 138 kilovolts.

4.9.11.A.12: The following requires approval in accordance with Section 3.3.4, 100' Notice Procedure. The PDSD Director may forward the request to the Design Review Board (DRB) for design review and recommendation.

- Water pumping and storage facility upgrades or expansions, provided:
(1) Existing setbacks are not altered.
(2) Use Specific Standards 4.9.11.A.5, .9, .11, are met.

3. Per Section V, Appeal: To modify any of the required UDC standards, provide a City Manager Waiver in accordance with Section V of the Administrative Directive 1.07-6 with the formal Development Package or the CIP.
https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_admin/1_07_06__code__compliance_in__city__improvement__projects

4. Dimensional Standards
Maximum lot coverage: 15% (Non-Residential)
Maximum height: 30’-0”

Perimeter yard (setbacks):
• South (adjacent W Sweetwater Dr): 20’-0” from right-of-way
• North (adjacent P-1 zoning): 0’-0”
• East (adjacent P-1 zoning): 0’-0”
• West (adjacent RX-1): 20’-0”

5. Development Standards

a. Parking ratios (UDC 7.4.4-1). Ensure compliance with UDC 7.4.6, Design Standards.
No proposed building provided; (1 parking stall per 500 square feet of Gross Floor Area)

6. Ensure pedestrian circulation is accessible, a minimum of 4’-0” wide connecting all areas of development and to any street frontage (TSM 7-01).

7. Any proposed signage (monument, pylon, building) will be per separate sign permit. Show location and dimensions on submitted site plan.

8. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at Jeffrey.Cassidy@tucsonaz.gov.

UDC (Unified Development Code): https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-16
Administrative Manual: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-8283
Technical Standards Manual: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-10261
TW New Area Development * REVIEW COMPLETED Based on the information provided, Tucson Water has no objections to the proposed development.
Please coordinate with Tucson Water’s Planning and Engineering Division regarding any questions related to Tucson Water.
For further assistance, please contact John Van Winkle, Chief Engineer for Tucson Water Planning and Engineering, at John.Vanwinkle@tucsonaz.gov.
This parcel falls within an Archaeological Sensitivity Zone. For additional information or requirements, please contact the City of Tucson Historic Preservation Office at (520) 837-4984 or PDSDHistoric@tucsonaz.gov.
The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to Deepesh Raj Dawadi
(Engineering Manager) at Deepeshraj.Dawadi@tucsonaz.gov