Plan Number: TP-PRE-0925-00196
Parcel: 14111026A

Review Status: Approved

Review Details: PRE-APPLICATION CONFERENCE REVIEW v.1

Plan Number - TP-PRE-0925-00196
Review Name: PRE-APPLICATION CONFERENCE REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Fire New Construction * REVIEW COMPLETED TP-PRE-0925-00196 •Pre-Application Conference Review v1 • 7755 S OLD VAIL RD TUCSON, AZ 85747:
1. Provide Knox access at gates. IFC 24, 503.6, 506.1
2. Verify hydrant coverage. IFC 24, 507.5.1
3. Maintain aerial access in accordance with IFC 2024, Appendix D 105.1 (please note TFD will not accept trees with mature height over 20' on the aerial access side of the building.
4. Drive aisles widths (including gates) will need to be a minimum 20' (IFC 2024, 503) with the exception of the aerial access lane minimum 26' (D 105)
Questions: patricia.shelton@tucsonaz.gov / 520.837.7082
ROW Engineering Review * REVIEW COMPLETED CDRC TRANSMITTAL DEPARTMENT OF TRANSPORTATION RIGHT OF WAY ENGINEERIN REVIEW : KE&G TUCSON CAMPUS WITH OFFICE BUILDING, MAINTENANCE SHOP & WAREHOUSE ACTIVITY NO: TP-PRE-0925-00196 ADDRESS: 7755 S OLD VAIL RD
1) AS REFERANCED IN CHPATER 25 -
Sec. 25-39. Special requirements in business districts.
Curb cuts and driveways shall conform to the following requirements in all business zoned districts:
Maximum curb cut width . . . . . 35 feet
Maximum driveway width at the property line . . . . . 30 feet
Minimum distance between curb cuts or driveways . . . . . 20 feet
Maximum number of curb cuts or driveways per 100 feet of street frontage . . . . . 2
Minimum distance of curb cuts from street light standards, or catch basins . . . . . 5 feet
Minimum distance from a fire hydrant of city water hydrant . . . . . 20 feet
Minimum distance from end of a curb return . . . . . 4 feet
OR
From a curb line on a cross street at a street intersection . . . . . 20 feet
whichever is more restrictive.
(Ord. No. 2657, § 1, 10-19-64)
Sec. 25-40. Special requirements in industrial districts.
(a) Curb cuts and driveways shall conform to the following requirements in all industrial zoned districts:
The provisions established for curb cuts and driveways in section 25-39 for business zoned districts shall prevail in all
industrial zoned districts for properties fronting on a through street, as defined in this Code, or on a major street as shown on
the latest major streets and routes plan on file with the city engineer.
(b) If the property does not front on a through or major street, only the following provisions shall prevail:
Minimum distance of curb cut from street light standards or catch basins . . . . . 5 feet
Minimum distance from a fire hydrant or city water hydrant . . . . . 20 feet
Minimum distance from end of a curb return . . . . . 4 feet
OR
from the curb line on a cross street at a street intersection . . . . . 23 feet
whichever is the more restrictive.
(Ord. No. 2657, § 1, 10-19-64)
2) TECHNICAL STANDARDS MANUAL - SECTION 10-01.4.3 -- Driveways
A. Driveway aprons will be of portland cement concrete (PCC) constructed to City of Tucson Standards, with a standard length of eight feet from the front of the curb to the back of the apron.
B. Curb returns may be used in place of standard curb cuts only when one or more of the following conditions occur.
1. The ADT of the driveway exceeds 100;
2. The points of access to a property should be limited for traffic control and other reasons;
3. Local conditions occur which involve speed, the amount of truck traffic, or the type of development and which, in the opinion of , require curb returns; or,
4. When intersections a collector or arterial street.
3)SIDEWALK ACCESS RAMPS ARE TO CONFORM TO CITY STANDARD 207 SHEET 4 SINGLE DIRECTION CURB ACCESS RAMP
If you have any further questions or concerns please feel free to email me at Zane.swenson@tucsonaz.gov. I will research and address concerns and get back to you.
Site Engineering * REVIEW COMPLETED Permit: TP-PRE-0925-00196
Location: 7755 S OLD VAIL RD
Review Date: 10/15/2025

Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage-manual-searchable.pdf
Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-retention-detention-manual.pdf

Site Engineering Comments:
1. A Storm Water Pollution Prevention Plan (SWPPP) and dust control permit will be required for this development.
2. A Drainage report to show full compliance with first flush retention/balanced basin detention requirements. Refer to the Design standards for Stormwater Detention and Retention Chapters 2, 3, & 4. Drainage report content and format requirements can be found in chapter 10 of the DSSDR as well. Drainage must meet the Rita Ranch master drainage requirements.
3. The covered parking canopies will be required to all be setback a minimum of 1 foot from the PAALS. UDC 7.4.6.F.2
4. Provide Waste Stream Calculations for the site according to TSM 8-01.8.0
5. A grading plan with cut/fill quantities and area of disturbance will be required. TSM 2-01.0.0
6. Clearly show downspouts and sidewalk scuppers. to ensure that stormwater from roof drains, up to and including flow from the ten-year storm event, does not pass over sidewalks per Technical Standards Manual 7-01.4.3E.
7. Pedestrian circulation is required to connect all buildings, dumpster areas, and the sidewalk on the street frontage per TSM 7-01.3.3.
This review is for Pre-Application purposes. Please be aware that additional comments may be forthcoming during submission process.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
Site Landscape * REVIEW COMPLETED CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: KE&G TUCSON CAMPUS WITH OFFICE BUILDING, MAINTENANCE SHOP & WAREHOUSE
ACTIVITY NO: TP-PRE-0925-00196
ADDRESS: 7755 S OLD VAIL RD
ZONING: I-1 INDUSTRIAL ZONE
LAND USE: COMMERCIAL

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by the Site Landscape and NPPO section to ensure compliance with the applicable UDC development criteria and Technical Standards.

SITE LANDSCAPE/NPPO COMMENTS:

1. A NPPO or a NPPO Waiver is required per UDC 7.7. SEE UDC 7.7.3. APPLICABILITY; UDC 7.7.4 NPPO GENERAL PROVISIONS AND STANDARDS; UDC 7.7.4.C. PLAN APPROVAL PRIOR TO PERMITTING; UDC 7.7.4.D. PROFESSIONAL EXPERTISE 7.7.5.C.5; ALSO SEE AM 2-11.3.0 PERMITTED EXCEPTIONS. PDSD will provide the applicant with the NPPO Waiver form upon request.

2. UDC 7.6.2. APPLICABILITY
The provisions of this section apply to the following:
A. All new developments require the preparation of landscape plans that adhere to UDC 7.6.4 and Administrative Manual 2-10.

3. Provide the required number of trees in all vehicular parking areas (1 tree to 4 parking spaces) per UDC 7.6.4.B.1. Trees are to be distributed evenly throughout the parking area, UDC 7.6.4.1.B.1, UDC Technical Standards Manual 5-01-.3.2 and UDC 7.6.4.B.1.a.

*EXEMPTIONS: Structurally covered or underground garages.

4. A street landscape border is required along Old Vail Road per UDC 7.6.4.C-2 and Table 7.6.4-1. See UDC 7.6.4.C for landscape border requirements. Commercial land use along MS&R and non-MS&R requires a 10’ street landscape border.

5. A drip irrigation plan and details are required for all proposed landscape planting areas.

6. DTM review is required for all planting and irrigation in the ROW prior to the approval of the development package. Reach out to David Marhefka (david.marhefka@tucsonaz.gov) if necessary for this project.

7. All landscape plans shall incorporate water conserving design as defined in UDC Section 7.6.6, Use of Water, and as described in the Technical Standards Manual 5.01-5.11.

8. A Commercial Rainwater Harvesting plan is required: See Technical Standards Manual 4-01.3.0 RAINWATER HARVESTING PLAN. A Rainwater Harvesting Plan shall be submitted with all applications for commercial developments at which landscaping is required.

9. Coordinate the Landscape Plan, Commercial Rainwater Harvesting Plan and the Civil Grading Plans to have identical basin size, grades/percent slopes, spot elevations and curb cut inlet and outlet locations.

10. Maximize rainwater harvesting across the site into all landscape areas, including the street landscape borders and planting islands for the required trees in the parking area.

11. A separate irrigation water meter is required. Please label irrigation meter as “irrigation only”. See TSM 4-01.6.0

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
520.837.4923
Site Zoning * REVIEW COMPLETED CDRC Thursday Pre-Submittal Transmittal
FROM: Ramiro Olivarez
PDSD Zoning Review
PROJECT: Pre-submittal meeting TP-PRE-0925-00196
Address: 7755 S OLD VAIL RD
Zoning: I-1 & I-2
Proposed Use: Mixed Use Development

TRANSMITTAL DATE: October 16, 2025

COMMENTS:
1. Comment: The proposed development must comply with the City of Tucson Unified Development Code (UDC) Administrative Manual Chapter 2-06 – Development Package. Building permits (demolition permit) can be submitted and reviewed concurrently with the development package but the building plans cannot be approved until the development package is approved and the building plans are reviewed for consistency.

2. Comment: This site is located in the 5.6.8.B. Approach Departure Corridors (ADC-2) DMAFB Overlay and must comply.

3. Comment: Administrative and Professional Office use is not an allowed Use in the ADC-2 Overlay.

Or

Exception – Demonstrate this site complies with UDC 5.6.8.3.b. and provide a “protected development plan was approved by Mayor and Council specifically for such prior to June 30, 2005”

Construction Services use is allowed in the I-1, I-2, and ADC-2 overlay zone with use specific standards, UDC 4.9.13.Q.

Commercial Storage use is allowed in the I-1, I-2, and ADC-2 zone with use specific standards, UDC 4.9.10.A and 4.9.13.Q.

Clarify which Industrial use is to be located at this site.

Clarify the proposed building use.

4. Comment: In the I-1/I-2 zone there is not a minimum lot size. UDC TABLE 6.3-5.A.

5. Comment: There is no maximum lot coverage for nonresidential use. UDC TABLE 6.3-5.A.

6. Comment: The height maximum is 75’ for I-1 and 140’ for I-2 for feet for nonresidential use. UDC TABLE 6.3-5.A.

7. Comment: Setbacks for a nonresidential use adjacent to a nonresidential zone is 0 feet and adjacent to a residential zone is 1 ½ (H). UDC TABLE 6.3-5.A.

8. Comment: A gas easement runs through the parcel and cannot be built on.

9. Comment: Ensure compliance with Table 7.4.4-1: Minimum Number of Motor Vehicle Spaces Required for Industrial Use Group is 1 space per 300 sq. ft. GFA.

Ensure compliance with Table 7.4.4-1: Minimum Number of Motor Vehicle Spaces Required for Industrial Use Group is 1 space per 1,000 sq. ft. GFA.

For more specific Industrial Use Group projects see Table 7.4.4-1.

Ensure compliance with Table 7.4.4-1: Minimum Number of Motor Vehicle Spaces Required for Commercial Storage on a single site is 1 space per 5,000 sq. ft. GFA, plus 1 space per 5,000 sq. ft. of outdoor storage area for the first 20,000 sq. ft. of outdoor storage area, plus 1 space per 10,000 sq. ft. of outdoor storage area over 20,000 sq. ft. of outdoor storage area.

Proposed future buildings upon submittal will require parking in addition to existing parking to meet requirements.

10. Comment: Ensure Motor Vehicle Use Area parking design is compliant with 7.4.6 of the UDC.

11. Comment: A motor vehicle off-street parking space must have a minimum width of ten feet when the side(s) of the parking space abuts a vertical barrier over six inches in height, other than a vertical support for a carport. (UDC7.4.6.D.2.b)

12. Comment: The minimum height clearance along access lanes and PAALs is 15 feet, except as follows. The minimum height clearance within parking garages may be less than 15 feet as permitted by the City ’s adopted Building Code. Building Code. UDC7.4.6.D.2.b)

13. Comment: Ensure compliance with Table 7.4.8-1: Minimum Required Bicycle Parking Spaces –
a. For Commercial Use Group Short-term Bicycle Parking is 2 spaces.
b. For Commercial Use Group Long-term Bicycle Parking is 1 space per 12,000 sq. ft. GFA, minimum requirement is 2 spaces

Ensure compliance with Table 7.4.8-1: Minimum Required Bicycle Parking Spaces –
c. For Industrial Use Group Short-term Bicycle Parking is none.
d. For Industrial Use Group Long-term Bicycle Parking is 1 space per 15,000 sq. ft. GFA. Minimum requirement is 2 spaces. Maximum required is 10 spaces.

Ensure compliance with Table 7.4.8-1: Minimum Required Bicycle Parking Spaces –
a. For Commercial Storage Short-term Bicycle Parking is none.
b. For Commercial Storage Long-term Bicycle Parking is 1 space per 40,000 sq. ft. GFA. Minimum requirement is 2 spaces. Maximum requirement is 10 spaces.

14. Comment: Ensure bike parking design is compliant with 7.4.9 of the UDC.

15. Comment: Storage Use Group Loading areas required are none, unless;

Required Loading areas for Commercial Storage w/o Direct Vehicular Access 50,001 to 100,000 sq. ft. GFA is 1 Type A loading area required.

16. Comment: Old Vail Rd is a Major Street & Route. Per UDC 6.4.5.C.2.a For nonresidential and multifamily development abutting an Arterial or Collector Street the minimum required street perimeter yard is ten feet, as measured from the existing or future property line as determined by the adopted Major Streets and Routes Plan, whichever is greater.

17. Comment: Ensure the site complies with section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual.
a. The pedestrian circulation paths must comply with 7-01.3: Within all development, a continuous pedestrian circulation path is required as follows:
A. This path must connect all public access areas of the development and the pedestrian circulation path located in any adjacent streets.
B. The areas within the development which must be connected include, but are not limited to, all buildings, all bicycle and vehicle parking areas, all recreation areas, all dumpster areas, and all other common use areas.

18. Comment: The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at Ramiro.Olivarez@tucsonaz.gov
TW New Area Development * REVIEW COMPLETED TP-PRE-0925-00196 (7755 S OLD VAIL RD TUCSON, AZ 85747)
KE&G Tucson Campus
Based on the information provided, Tucson Water has no objections to the proposed development and offers the following comments for your convenience:

Water service for this project will be provided by connecting to the existing 16" cement asbestos water main located on the west side of the parcel within the right-of-way along S. Old Vail Rd.

1. Additional information about the fire flow, the number, size and type of water meters needed for this development will need to be supplied to Tucson Water, to determine if modeling needs to be performed to verify the existing public water mains have the capacity necessary to serve the proposed development. This can be done via your interactions with the Tucson Water New Services Section
2. Any new on-site and off-site water mains needed to serve this development will need to be public water mains, constructed at the owner’s/developer’s expense.
3. When the fire flow requirements have been established by the local fire authority, the automatic sprinkler system demand, including the hose stream allowance, and the required fire flow are known, and a water fixture unit count has been conducted for the project using the 2018 International Plumbing Code, please contact Tucson Water’s New Services section by sending an e-mail to TW_COMMON@tucsonaz.gov to discuss:
• Potential points of connection to Tucson Water’s existing water distribution system. Please note that hydraulic modeling may need to be performed to verify which potential points of connection have the capacity necessary to serve the proposed development. If so, it can be arranged through Tucson Water’s New Services section.
• The number of water service lines, water meters, and meter sizes, necessary to serve this development.
• The advantages and disadvantages of installing the necessary water meters via Tucson Water’s Job Order Contract (JOC) process.
4. Note that a 10’ x 25’ easement is required for 3” or larger above ground meters, and 2” meters are the largest allowable underground meters.
5. If any other new domestic water, irrigation water, or fire water services are needed to serve this proposed development, please contact Tucson Water’s New Services Section by calling 520-791-5164 or by sending an email to TW_Common@tucsonaz.gov.

The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Abdullah Salman | Project Manager
Tucson Water - New Area Development
Abdullah.Salman@tucsonaz.gov