Plan Number: TP-PRE-0426-00092
Parcel: 103090310

Review Status: Requires Resubmit

Review Details: PRE-APPLICATION CONFERENCE REVIEW v.1

Plan Number - TP-PRE-0426-00092
Review Name: PRE-APPLICATION CONFERENCE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Building Official * REQUIRES RESUBMIT Review conducted by Mark Masek and Justin Eder.
Pre-Application Meeting Comments only. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. Cover Sheet Revisions
Please update the Cover Sheet as follows:
A. Code Review Note 1
The occupancy group identified in Code Review Note 1 appears to be associated with a different project. Please revise the occupancy classification to Group A-3 and update the description accordingly.
B. Change of Use
Please revise the description in Code Review Note 1 to accurately reflect the proposed scope of work, which includes a change of use involving the conversion of the existing storage area into a lobby, conference room, and restroom facilities.
C. Fire Protection Information
Please indicate whether a fire sprinkler system and fire alarm system are proposed. If a sprinkler system is proposed, identify the type of system.
Relevant code requirements include:
i. IBC Section 903.2.1.3 requires an automatic fire sprinkler system in Group A-3 occupancies where the occupant load is 300 or more.
ii. IBC Section 907.2.1 requires a fire alarm system in Group A occupancies where the occupant load attributable to the assembly use is 300 or more.
D. Code Review Note 7
Please revise Code Review Note 7, as it appears to contain information from another project.
2. Sheet A-3 Revisions
Please update Sheet A-3 as follows:
A. Second-Story Storage Area
Provide the use, occupant load, means of egress information, and maximum travel distance for the proposed second-story storage area.
B. Fire Separation Wall
As discussed during the meeting, please show the location of the proposed fire separation wall and identify:
The occupancy classification of the adjacent connected building; and
The fire-resistance rating and construction type of the proposed wall.
C. Accessibility
Clearly identify all accessible entrances and accessible exits on the floor plan.
D. Occupant Load Information
Provide the square footage, occupant load factor, and calculated occupant load for each room and space.
E. Platforms and Accessible Access
Provide construction documents and details for all proposed platforms, including any ramps or other accessible routes required to provide accessibility.
F. Main Entrance Capacity
As discussed during the meeting, the southernmost doorway on the east wall will be relocated adjacent to the proposed storefront entrance to establish the primary entrance. Please revise the plans to demonstrate that the main entrance provides a capacity of not less than 50 percent of the required egress capacity, in accordance with IBC Section 1030.2, Assembly Main Exit.
Please contact me if you have any questions about the above comments.