Plan Number: TP-PRE-0126-00029
Parcel: 121050070

Review Status: Approved

Review Details: PRE-APPLICATION CONFERENCE REVIEW v.1

Plan Number - TP-PRE-0126-00029
Review Name: PRE-APPLICATION CONFERENCE REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Fire New Construction * REVIEW COMPLETED TP-PRE-0126-00029 •Pre-Application Conference Review v1 • 2122 N CRAYCROFT RD TUCSON, AZ 85712:
Based on the information provided, TFD has the following comments:
1. Verify dead ends in excess of 150’ are provided with turnarounds. IFC, 2024, D103.4
2. Verify hydrant coverage. IFC 24, 507.5
Please reach out with any additional fire-related questions.
Questions: patricia.shelton@tucsonaz.gov / 520.837.7082
ROW Engineering Review * REVIEW COMPLETED DTM Review Comments -
1) Sidewalk will be required meeting PAG 200 standard along the Craycroft Rd Frontage & E Hampton St frontage with connection to Existing Curb access ramps.
2) Closure and Restoration of Curb line along Craycroft Rd meeting PAG standards with 6" curb for unused Curb cut
3) South Proposed driveway entry will to meet PAG 206 Standard detail w/cross slope not to exceed 2%
4) All driveway to meet PAG 206 Standard Detail with full Concrete construction up to back of sidewalk.

Zane Swenson - zane.swenson@tucsonaz.gov
Site Engineering * REVIEW COMPLETED Permit Activity Number: TP-PRE-0126-00029
Project: Development of a new outpatient facility. Site to receive new access to ROW, parking, and utilities.
Location: 2122 N CRAYCROFT RD
Review Date: 2/26/2026
Reviewer: Joe Macaulay – Civil Engineer – Site Engineering
Related Cases:

*This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-6 and Technical Standards Manual (TSM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code.*
City of Tucson Code: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes
Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage-manual-searchable.pdf
Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-retention-detention-manual.pdf

Site Engineering Review Comments:
1. A geotech report associated with the new build will be required at submission of the DP.
2. A drainage report with full compliance of first flush retention/critical basin detention requirements. Refer to the DSSDR chapters 2, 3, & 4. Content and format requirements for the drainage report can be found in chapter 10 of the DSSDR.
3. Grading plan sheet(s) to include cut/fill quantities and total area of disturbance. A Storm Water Pollution Prevention Plan (SWPPP) and dust control permit will be required for area of disturbance greater than one acre. TSM 2-01.0.0
4. Provide the additional details to the site plan for submittal to DP.
a. Show downspouts and scuppers on site plan. Must match DP and building permit. TSM 7-01.4.1.E
b. Pedestrian circulation is required to connect all buildings, dumpster areas, common areas, and the sidewalk on all the street frontages. Continue sidewalk along Hampton St east of the driveway apron. Pedestrian circulation currently does not show connection to Hampton St. TSM 7-01.3.3
i. For application of PDMR please contact Nick Ross and Stephen Blood: Nicholas.Ross@tucsonaz.gov, Stephen.Blood@tucsonaz.gov
c. PAAL width is less than required 24’ width requirement. UDC Table 7.4.6-2
d. Provide the Waste Stream Calculations for the entire site. TSM 8-01.8.0
e. Show sight visibility triangles (SVT). TSM 10-01.5.0
f. Provide trash enclosure details including 14’x40’ maneuverability for operation. TSM 8-01.5.0 & TSM 8-01.9.0

This review is for Pre-Application purposes. Please be aware that additional comments may be forthcoming during submission process.

If you have any questions or concerns, please contact Joe Macaulay at Joe.Macaulay@tucsonaz.gov.
Site Landscape * REVIEW COMPLETED PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: DEVELOPMENT OF A NEW OUTPATIENT FACILITY; TWO STORY FACILITY WITH ASSOCIATED PARKING
ACTIVITY NO: TP-PRE-0126-00029
ADDRESS: 2122 N CRAYCROFT RD
ZONING: OFFICE ZONE (O-3)
LAND USE: MEDICAL FACILITY/COMMERCIAL LAND USE PER UDC TABLE 7.6.4-1
02.25.2026

THE COMMENTS PROVIDED ARE PRELIMINARY AND ARE NOT TO BE ASSUMED AS A COMPLETE REVIEW OF THE PROPOSAL. DURING THE DEVELOPMENT PACKAGE REVIEW PROCESS, A FULL REVIEW WILL BE MADE BY THE SITE LANDSCAPE/NPPO REVIEW SECTION TO ENSURE COMPLIANCE WITH THE APPLICABLE CITY OF TUCSON UNIFIED DEVELOPMENT CODE, TECHNICAL STANDARDS MANUAL AND ADMINISTRATIVE MANUAL REQUIREMENTS FOR SITE LANDSCAPE, NATIVE PLANTS AND RAINWATER HARVESTING.

SITE LANDSCAPE/NPPO COMMENTS:

1. This site has been previously developed and protected native plants are not present on site. No NPPO is required for this development.

2. UDC 7.6.2. APPLICABILITY
A. The provisions of this section apply to the following: All new developments require the review and approval of a site landscape plan set. Preparation of the landscape plans shall adhere to UDC 7.6 and Administrative Manual 2-10.

3. Parking lot canopy trees are required at 1 tree for every 4 parking spaces provided, see UDC 7.6.4.B. Structurally covered parking spaces do not count toward the ratio, see UDC 7.6.4.B.1.c. (8). Trees are to be distributed evenly throughout the parking area, see UDC 7.6.4.1.a.(1). See Technical Standards Manual 5-01.3.0 for additional landscaping in vehicular use area requirements.

4. Interior landscape borders per UDC 7.6.4.C.3 and Table 7.6.4-1 and proposed Commercial Land Use:
A. The east property boundary of the site requires a 10’ interior landscape border and a 5’ screen located on the property line.
B. The southwest border adjacent to the Office Zone requires a 10’ landscape border and a 5’ screen located on the property line.
C. The south/southeast border adjacent to the Residence Zone requires a 10’ landscape border and a 5’ masonry wall on the property line.

5. Street landscape borders per UDC 7.6.4.C.2 and Table 7.6.4-1 and proposed Commercial land use along MS&R and non-MS&R:
A. N Craycroft Rd requires a 10’ landscape border and a 30” screen located on the project side of the ROW/Future ROW.
B. E Hampton St requires a 10’ landscape border and a 5’ screen located on the project side of the ROW/Future ROW.

6. A drip irrigation plan and details are required for all proposed landscape planting areas.

7. DTM review is required for all planting and irrigation in the ROW prior to the approval of the development package. Reach out to David Marhefka (david.marhefka@tucsonaz.gov) for review and approval if applicable for this project.

8. All landscape plans shall incorporate water conserving design as defined in UDC Section 7.6.6, Use of Water, and as described in the Technical Standards Manual 5.01-5.11.

9. A Commercial Rainwater Harvesting plan is required: See Technical Standards Manual 4-01.3.0 RAINWATER HARVESTING PLAN. A Rainwater Harvesting Plan shall be submitted with all applications for commercial developments at which landscaping is required. The Rainwater Harvesting Plan shall consist of two elements: a Site Water Budget and a Water Harvesting Implementation Plan. Preparation of the Rainwater Harvesting Plan elements requires coordination between project managers, site engineers and landscape architects from the inception of the project. The two elements of the Rainwater Harvesting Plan shall illustrate water harvesting how will meet 50% of annual landscape water demand, as required by the ordinance.

10. Coordinate the Landscape Plan, Commercial Rainwater Harvesting Plan and the Civil Grading Plans to have identical basin size, grades/percent slopes, spot elevations and curb cut inlet and outlet locations.

11. Maximize rainwater harvesting across the site into all landscape areas, including the street landscape borders and planting islands for the required trees in the parking area.

12. A separate irrigation water meter is required. Please label irrigation meter as “irrigation only”. See TSM 4-01.6.0. Or see City of Tucson Ordinance 10597 -- Sec. 6-182. Rainwater Harvesting Plan: Number 3 (a) A separate water meter connected to the main water supply; or (b) An irrigation sub-meter.

13. **If it is determined that any of the above provided site landscape standards cannot be met due to the nature of the development, then a Design Development Option (DDO) may be an option to gain partial relief from some landscape requirements, see UDC 3.11.1.B.3 for landscape and screening modifications allowed. A Board of Adjustment Variance to the UDC site landscape requirements is also a viable alternative. Please reach out to Mark Castro or Georgia Pennington with PDSD for more information on the DDO and Variance process. Mark.Castro@tucsonaz.gov – Georgia.Pennington@tucsonaz.gov

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
520.837.4923
Site Zoning * REVIEW COMPLETED CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review
FROM: Krista Hansen, Lead Planner
PROJECT: Pre-submittal meeting TP-PRE-0126-00029

Parcel: 121050070
Address: 2122 N CRAYCROFT RD
Zoning: O-3
Existing Use: Commercial Services: Medical Service – Outpatient
Proposed Use: Commercial Services: Medical Service – Outpatient

TRANSMITTAL DATE: 2/26/2026

COMMENTS:
1. Any proposed development must comply with the City of Tucson Unified Development Code (UDC) Administrative Manual Chapter 2-06 – Development Package (DP). Building permits can be submitted and reviewed concurrently with the development package but the building plans cannot be approved until the development package is approved and the building plans are reviewed for consistency.
2. The site is zoned O-3. The proposed use is Commercial Services: Medical Service – Outpatient, which is permitted, subject to use specific standards UDC 4.9.13.K.
3. The demolition of the existing offices will require a Commercial Demolition Permit and Historic Demolition Documentation (structures > 50 years old) www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/planning-amp-zoning/historic_demolition_application_form.pdf
4. Dimensional Standards for O-3 (UDC Table 6.3-3.A):
a. No maximum lot coverage for nonresidential
b. Maximum building height is 40’ for nonresidential
c. Street setbacks: 10’ to Country Club (west) and 20’ to Hampton St (north)
d. Setbacks to east and south property lines are 10’ or ¾ (H) height of the adjacent building wall, whichever is greater
5. Provide a pedestrian circulation path that connects all areas of development on-site and to any adjacent street frontage, including Hampton St (TSM 7-01).
6. Motor Vehicle parking ratios (UDC Table 7.4.4-1). Ensure compliance with UDC 7.4.6. Medical Service – Outpatient requires a minimum of 1 space per 200 SF of GFA. If parking spaces are lost due to adding a pedestrian connection to Hampton St, zoning recommends applying for a Parking Design Modification Request (PDMR). Please contact Nicks Ross at Nicholas.Ross@tucsonaz.gov or Stephen Blood at Stephen.Blood@tucsonaz.gov for more information.
7. Bicycle parking ratios (UDC Table 7.4.8-1). Ensure compliance with UDC 7.4.9. Medical Service – Outpatient requires 1 short-term parking space per 5,000 SF of GFA and 1 long-term parking space per 12,000 SF of GFA (min 2 spaces).
8. Electric vehicle supply equipment (EVSE) parking ratios (UDC Table 7.4.11-1). Ensure compliance with UDC 7.4.12. For Medical Service, 5% of the required parking spaces need to be EV Ready and 15% need to be EV Capable.
9. The minimum width of a two-way PAAL is 24’ per UDC Table 7.4.6-2. It appears that the two-way PAALs along the east and north sides of the building are only 22’.
10. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at krista.hansen@tucsonaz.gov.
TW New Area Development * REVIEW COMPLETED Based on the information provided, Tucson Water has no objections to the proposed development.
The building currently has one existing (2inch) meter. The service is connected to a 4-inch cement asbestos water main (C Zone) located on south of the building. Water pressure in this area is 85-92 PSI at an elevation of 2488 ft. Water pressure can vary by an additional 5 psi +/-. There is a fire hydrant in the NE corner of the property that should be capable of 1,000 gpm of fire flow.
Please note that there is designated easement located on the south side of the parcel. This easement is reserved for utility and/or access purposes as recorded in the property documentation.
If any new domestic water, irrigation water, or fire water services are needed to serve this proposed development, please contact Tucson Water’s New Services Section by calling 520-791-5164 or by sending an email to TW_Common@tucsonaz.gov.
The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to Kathryn Gerber (Engineering Manager) at Kathryn.Gerber@tucsonaz.gov.