Permit Number: TF-FOP-1225-01559
Parcel: 11518023A

Address:
1333 N ORACLE RD

Review Status: Requires Resubmit

Review Details: FIRE OPERATIONAL REVIEW v.1

Permit Number - TF-FOP-1225-01559
Review Name: FIRE OPERATIONAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2025 Fire Code Enforcement Fast PENDING ASSIGNMENT
12/08/2025 Commercial Structural Express REQUIRES RESUBMIT ACTIVITY NO. TF-FOP-1225-01559
ADDRESS: (1333 N ORACLE RD TUCSON, AZ 85705)

COMMENTS:
1. Please take a look at the example submission package that was emailed to all tent applicants several months earlier.
2. TENT
a. Size: 98 ft x 147 ft
b. Area: 14,406 sf
3. TENT PLAN
a. Thank You for submitting a floor plan that shows the display tables.
b. Please LOCATE/LABEL THE FOLLOWING ON THE PLAN (FOR INSPECTION PURPOSES BY TUCSON FIRE DEPARTMENT):
i. LIGHTED EXIT LIGHTS WITH POWER BACKUP
ii. EMERGENCY LIGHTS WITH POWER BACKUP
iii. FIRE EXTINGUISHERS
iv. NO SMOKING
v. ELECTRIC POWER GENERATOR(S) - IF USED
4. STRUCTURAL CALCULATIONS
a. NOTE: Structural Calculations exhibits and Anchoring System used shall be sealed/signed/dated by an Arizona licensed Structural Engineer.
i. Please have a structural engineer seal/sign/date the document.
b. The submitted exhibit also mentions that the installer is responsible for providing the anchorage system to resist the lateral loads.
c. i. Please submit the anchoring system you will be using (this should show the thickness, and the length should you be using stakes).
d. ii. Please indicate their locations on your floor plan.
e. iii. Please indicate how many stakes (if this is what you are using) you will be installing at each post base plate location.
f. iv. Show the resistance each stake will provide.
g. v. Show the total resistance at each post base plate and illustrate that it is enough to resist the lateral forces.
h. vi. Indicate the status of the soil structure is being installed at.
5. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
12/02/2025 TFD Application Completeness Check Express REVIEW COMPLETED