Review Status: Requires Resubmit

Review Details: FIRE OPERATIONAL REVIEW v.1

Permit Number - TF-FOP-1026-01388
Review Name: FIRE OPERATIONAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2026 Fire Code Enforcement Fast PENDING ASSIGNMENT
10/20/2026 Commercial Structural Express REQUIRES RESUBMIT ACTIVITY NO. TF-FOP-1026-01388
ADDRESS/PARCEL: (3220 N CRAYCROFT RD TUCSON, AZ 85712)
TF-FOP-1026-01388 (3220 N CRAYCROFT RD TUCSON, AZ 85712)
Submit your revised drawings along with a ***detailed response letter***, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. Per IBC 2024 Please have an Arizona Licensed Structural Engineer seal/sign/date the structural calculation and membrane structure drawings signifying that according to his analysis the membrane structure design/structural calculation will comply in Arizona.
2. Please submit the anchoring system you will be using (this should show the thickness, and the length should you be using stakes).
3. Please indicate their locations on your floor plan.
4. Please indicate how many stakes (if this is what you are using) you will be installing at each post base plate location.
5. Show the resistance each stake will provide.
6. Show the number of stakes and total resistance at each post base plate, illustrate that it is enough to resist the lateral forces.
7. Floor Plan
a. Please submit this drawing that locates/label all the parts required such as fire extinguisher, exit sign, emergency lights, no smoking, location of stakes (or other means) how many stakes at each location, electric power generator if used, etc. (please see example floor plan example previously sent to all tent applicants).
8. Please resubmit.
10/19/2026 TFD Application Completeness Check Express REVIEW COMPLETED