Permit Number: TF-FOP-1025-01412
Parcel: 13220007H

Review Status: Requires Resubmit

Review Details: FIRE OPERATIONAL REVIEW v.1

Permit Number - TF-FOP-1025-01412
Review Name: FIRE OPERATIONAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2025 Fire Code Enforcement Fast PENDING ASSIGNMENT
11/06/2025 Commercial Structural Express REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please ensure the referenced codes used in the design of this project are the 2018 IBC or the 2024 IBC and remove all references to other Codes such as CBC.
Please provide structural design criteria, calculations and construction drawings for the site at Tucson, AZ and the 2018 IBC prepared and sealed by an Arizona Registrant that adequately show the scope of work and compliance with the adopted building codes. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please provide structural design and calculations to reference the codes adopted and amended by the City of Tucson. IBC 107.2. For example, the 2018 IBC, 2024 IFC etc.
3. Please take note of our wind speed amendment.
Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following:
Risk Category I – 100 mph
Risk Category II – 105 mph
Risk Category III – 110 mph
Risk Category IV – 115 mph
4. Please note construction drawings are to be sealed and dated by an Arizona licensed registrant. IBC 107.1 and amend the drawings to show or include the following information.
5. Please provide an installation/staking design, calculations and construction drawing, prepared by an Arizona licensed designer, seal, signed and dated reflecting the conditions for the site in Tucson, AZ. IBC 107.1 Please include the following information in the design criteria.
11/03/2025 TFD Application Completeness Check Express REVIEW COMPLETED